ADV200 SP • Quick start up guide - Specification and installation
Step 1 - Connections
3.
Insert an enabling contact between terminals 7 and S3 (Enable the drive and +24V inputs) on the R-
ADV200 board.
Connection of the drive enabling contact
R21R24 5
6 C1 7
8
9 10 11 12 C2 C3 S3
R11R14 1
2
3
4 S1+S1- 13 14 IS1 IC1 IC2 IS2
Enable
Connection of the drive enabling contact with Safety function (SIL2 configuration)
R21R24 5
6 C1 7
8
9 10 11 12 C2 C3 S3
R11R14 1
2
3
4 S1+S1- 13 14 IS1 IC1 IC2 IS2
Enable
5
4
3
2
1
Strip T2
(Regulation terminals)
Safety Input / Output connector
Strip T1
(Regulation terminals)
4.
Checks to be performed before powering the drive
• Check that the power supply voltage is in the 450 ... 75
0Vdc
range.
• Check that the Drive output terminals (U, V and W) are properly connected to the motor.
• Check that all the terminals in the drive control circuit are properly connected. Check that all control
inputs are open.
•
Powering the Drive: once the above checks have been completed, apply power to the drive and go on
to the next step in the procedure.
Powering the drive
• After completing all the checks described above, power the drive and proceed to Step 2.