ADV200 SP • Quick start up guide - Specification and installation
5.1.6 Input mains choke (L1)
Sizes ADV200 SP-1015 ... 61600:
Integrated on DC-link.
Sizes ADV-...-DC: not available
.
5.1.7 Motor connection
ADV200 SP-1015 ... 61600
M
3 ph
L1 L2 L3 BR1 BR2 C
D
U
V
W
Note: terminals L1-L2 and L3 are not present in -DC versions.
5.1.8 Braking unit connection (optional)
L1 L2 L3 BR1 BR2 C
D
U
V
W
Braking resistor
Note!
ADV200 SP-...-4
Terminals BR1/BR2 are standard up to size ADV200 SP-3300, optional in sizes ADV200 SP-4370 ... 5750, larger sizes
are not used.
From size ADV200 SP-5900 an optional external BUy braking unit can be used and connected to terminals C and D.
Refer to the BUy handbook for further information.
Recommended combination braking resistors: see
paragraph 10.4
.
ADV200 SP-...-4-DC
Terminals BR1/BR2 are not present.
An optional BUy braking unit connected to terminals C and D can be used. For further details reference should be
made to the BUy manual.
You MUST set the parameters for controlling braking resistance overload (MENU 22.6) to detect overheating of
the braking resistance. Without this information on the resistance used, you have to monitor the overtempera
-
ture switch on the resistance. Overheating may be caused by:
•
ramp times too short or braking too long
•
wrong braking resistance size
• input voltage too high
•
defective braking transistor on inverter or on braking module.
The overtemperature switch can be connected to the auxiliary contacts of the power supply contactor in order
to disable the drive in case of failure.