ADV200 SP • Quick start up guide - Specification and installation
5.4.3 RS 485 multi-drop connection
For the multi-drop connection, the
OPT-RS485-ADV
optional card must be installed on each drive; the ends of
the connection must have
S1
termination switch set to ON (for point 3: ON only on the first).
The multi-drop connection is always galvanically insulated.
Up to 20 drives can be connected; the maximum length of the connection is 200 meters.
1) Multidrop connection between ADV200 and an industrial PC with RS485 output
See figure 5.4.3.1. The connection requires:
• an optional
OPT-RS485-ADV
card for each ADV200,
• shielded wires to connect the
OPT-RS485-ADV t
o the PC.
2) Multidrop connection between ADV200 and a PC with RS232 output
See figure 5.4.3.2. The connection requires:
• an optional
OPT-RS485-ADV
card for each ADV200,
• shielded wires to connect the
OPT-RS485-ADV
to the PC, and an optional
PCI-COM
adapter (code
S560T).
3) Multidrop connection between ADV200 and a PC with USB output
See figure 5.4.3.3. The connection requires:
• an optional
OPT-RS485-ADV
card for each ADV200,
• a
USB-RS485
Serial converter interface (8S8F60).
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
A
EQP
B
nero
giallo
arancione
XS
XS
XS
XS
INDUSTRIAL PC,
PLC. etc
(WITH RS485)
Termination = ON
Female
Figure 5.4.3.1: Example of Multidrop connection between ADV200 and an industrial PC with RS485 port
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
ADV200
A
ON
S1
OFF
EQP
B
OPT-RS485-ADV
3
5
7
XS
XS
XS
XS
PCI-COM
XS1
XS2
PC with RS232
9
Male
ON
S1
OFF
Figure 5.4.3.2: Example of Multidrop connection between ADV200 and a PC with RS232 port