ADV200 SP • Quick start up guide - Specification and installation
67
Index Error message shown
on the display
Sub-code
Description
4
Error in motor connection.
Solution
:Check the motor connection, set the value of the direct current of the motor to 1/3 and
perform the motor autotune procedure. Then increase the direct current until autotuning is executed.
The penultimate value is the nominal current value at which the drive performs autotuning.
5
While running self-tuning the ESC key was pressed or the enable contact was opened or an alarm
occurred. The
Autotune
command was sent with the drive in the alarm condition
Solution
: Eliminate the reason for the alarm, remove the reason for the opening of the enable contact,
reset alarms.
6
A setting performed by the
Autotune
function produced a parameter value outside the min or max
range.
Solution
: Check the motor plate data or drive and motor sizes have been combined incorrectly.
7
The
Autotune
command was sent without being enabled.
Solution
: Close the enable contact before sending the
Autotune
command
8
Internal calculation error concerning IGBT control
Solution
: Perform autotuning once more, if the problem persists, contact the Gefran technical support
centre.
9
The drive has measured a stator resistance value exceeding the set limit.
Solution
: contact the Gefran technical support centre.
10
The drive has measured a stator resistance value below the set limit.
Solution
: contact the Gefran technical support centre.
11-12
Measurement of DTL internal compensation voltage outside accepted range.
Solution
: check connection between drive and motor.
If correct, the drive is faulty, contact the Gefran technical support centre.
13-14
Measurement of DTS internal voltage outside accepted range.
Solution
: check connection between drive and motor.
If correct, the drive is faulty, contact the Gefran technical support centre.
15 - 16 -17
LS leakage inductance value outside accepted range.
Solution
: Perform autotuning once more, if the problem persists, contact the Gefran technical support
centre.
18-19
Measurement of Im magnetising current outside accepted range.
Solution
: Perform autotuning once more, if the problem persists, contact the Gefran technical support
centre.
20-21
Measurement of Rr rotor resistor outside accepted range.
Solution
: Perform autotuning once more, if the problem persists, contact the Gefran technical support
centre.
Solution:
If the message appears with a value other than 0, follow the instructions supplied for each particular case
and repeat
Autotune
. This should be performed using the wizard function available from the keypad (STARTUP WIZ-
ARD) and the Tool software on the PC.
Pay attention to all motor plate data parmaeters, especially:
-
Rated speed
,
Motor rated speed
in rpm.
-
Rated frequency
,
Motor rated frequency
in Hz
-
Pole pairs
,
Motor pole pairs
Take care not to set the
Rated speed
parameter to the synchronous speed. The value of the
Rated speed
parameter
must be less than: [(
Rated frequency
* 60) /
Pole pairs
].
If the problem persists even after following the instructions supplied, confirm the values of the motor plate data
parameters, execute the
Take parameters
command but not
Autotune
..
6
Power config
Condition:
may occur during recognition of power cards. If this message is displayed, it is not possible to drive the
motor.
0020H-32
The power card is configured for a drive that is incompatible with the regulation card
0021H-33
The configuration of the power card is not compatible with the regulation card