10
ADV200 SP • Quick start up guide - Specification and installation
2.1 Drive type designation
The main technical characteristic of the drive are showed in the product code and in the nameplate.
I.e. product code:
ADV200-SP -EH 1 040 -K B X -4 -DC -SI
Safety card
EXP-SFTy-ADV inclusa
DC bus power supply version
Rated voltage :
4
= 400
V
ac
4A = 460
V
ac
Software:
X = standard
Braking unit:
X = non included
B = included
Keypad:
X = not included
K = included
Drive power, in kW:
015 = 1.5 kW
022 = 2.2 kW
030 = 3.0 kW
040 = 4.0 kW
055 = 5.5 kW
075 = 7.5 kW
110 = 11.0 kW
150 = 15.0 kW
185 = 18.5 kW
220 = 22.0 kW
300 = 30.0 kW
370 = 37.0 kW
450 = 45.0 kW
550 = 55.0 kW
750 = 75.0 kW
900 = 90.0 kW
1100 = 110.0 kW
1320 = 132.0 kW
1600 = 160.0 kW
Mechanical drive sizes:
1 = size 1
2 = size 2
3 = size 3
4 = size 4
5 = size 5
6 = size 6
External heatsink drive models with IP54 protection degree
Drive ADV200 SP series
Identification Nameplate
Type :
ADV200-SP-2075 -KBX-4
S/N: 07012345
Inp:
400Vac-15%
5%
50/60Hz
3Ph
14A@400Vac 12,6A@480Vac
350-750Vdc 18A@540Vdc
Out : 0-480Vac 500Hz 3Ph 7,5kW@400Vac 10 Hp @ 460Vac
7,5kW 16,5A @400V
14,9A@460V Ovld. 110%-60s
5,5kW 13A @400V
11,7A@460V Ovld. 150%-60s
÷
Modello inverter
Numero di serie
Ingresso
(tensione di alimentazione, frequenza,
Corrente di ingresso a coppia costante)
Uscita
(tensione, frequenza, potenza, corrente,
sovraccarico CT e sovraccarico VT)
Approvazioni
GEFRAN DRIVES AND MOTION S.R.L.
via G.Carducci, 24 I-21040-Gerenzano (VA)
Made in Italy
Factory ID: G
IND.CONT.
EQ 31 KF
Firmware & cards revision level nameplate
Cards revision
Firmware revision
Power
Regulation
Safety
Braking unit
Software
revision
Product
configuration
Firmware
HW release
S/N
07012345
Prod.
Release
D
F
P
R
S
INT-P
SW . CFG
CONF
2.00
-.G
-.L
10.10.10
A2
The inverter must be selected according to the rated current of the motor.
The rated output current of the drive must be higher than or equal to the rated current of the motor used.
The speed of the three-phase motor is determined by the number of pole pairs and the frequency (nameplate,
data sheet) of the motor concerned.
Operation above the rated frequency and speed of the motor must take into account the specifications given by
the manufacturer losses (bearings, unbalance etc.). This also applies to temperature specifications for continu
-
ous operation under 20 Hz (poor motor ventilation, not applicable to motors with external ventilation).
Содержание ADV200 SP Series