ADV200 SP • Quick start up guide - Specification and installation
75
Sizes
f
sw
Switching frequency
Derating factor
Default
Higher
K
t
K
Alt
K
f
(4)
(2)
(3)
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 Hz
1030
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.55
0.4
1040
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.55
0.4
1055
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
2075
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
2110
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
2150
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
3185
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
3220
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
3300
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
4370
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
4450
4
6, 8, 10, 12
0.9
1.2
1
1
0.85
0.7
0.6
0.5
4550
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
5750
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
5900
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
51100
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
61320
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
61600
4
6, 8
0.9
1.2
1
1
0.85
0.7
0
0
Note!
In Light Duty mode the switching frequency is set at 4 kHz for sizes up to 61600.
If, in the Heavy duty mode, the factory setting of
Switching freq mode
(PAR: 568) is changed from 0=Fixed to 1=Vari-
able, the switching frequency is controlled by the temperature of the drive heat sink and the output frequency. For further
information see the Functions and Parameters manual, menu 4.9.
Installation altitude above
sea level
K
t
Output Current derating factor at Ambient Temperature of:
20°C
25°C
30°C
35°C
40°C
45°C
50°C
0 … 1000 m
1
0.95
0.90
Input voltage derating factor
Kv
2
(
6)
: Derating factor of the input voltage based on altitudes
Figure 9.6.1: K
v
2
derating factor based on altitudes
0
1000
2000
3000
4000
0.7
0.8
0.9
1.0
Installation Altitude a.s.l. (meters)
Derating Kv
Installation
altitude
K
V
2
Derating factor
(6)
Mains voltage [V]
m (s.l.m.)
380
V
Ac
400
V
Ac
415
V
Ac
440
V
Ac
460
V
Ac
480
V
Ac
≤ 2000
100%
100%
100%
100%
100%
100%
≤ 2250
100%
100%
100%
100%
100%
97%
≤ 2500
100%
100%
100%
100%
98%
94%
≤ 2750
100%
100%
100%
100%
96%
92%
≤ 3000
100%
100%
100%
97%
93%
89%
≤ 3250
100%
100%
99%
94%
90%
86%
≤ 3500
100%
100%
96%
91%
87%
83%
≤ 3750
100%
96%
93%
88%
84%
80%
≤ 4000
98%
93%
90%
85%
81%
78%
If the voltage derating factor is not considered, may occour a drive breakdown.