Fig.13
3.
Switch on the power supply.
4.
Activate automatic programming mode (keep reset key pressed for 3 - 7 sec.),
see .
5.
The learning process starts automatically 1 - 2 seconds after reset.
®
Red steady light for 1 - 2 seconds.
As long as the actuated position has not been saved, the position of the non-
actuated position is signalled within the tolerance with the LED as steady light
and additional flashing of the LED, see Section 6.5.2, Page 32 .
6.
Activate solenoid valve Y1 (activate by operating the manual override device
or by actuation of the higher-order control).
Learning is completed when actuated and non-actuated position have been
detected and saved. If voltage is only switched off with one learnt position, the
position already learnt is discarded.
If the actuated and non-actuated positions have been detected and learnt, the
saved positions are retained when the device is switched back on again
following disconnection of the voltage supply. If the positions of the non-
actuated and actuated position are saved, the detection of every position
outside the position tolerance is signalled by the yellow or green LED flashing,
see Section 6.5.2, Page 32.
7.
Deactivate the solenoid valve.
®
Steady light green (with DIP1=0) with additional flashing of the yellow LED or
yellow steady light (with DIP1=1) with additional flashing of the green LED,
see Section 5.4, Page 26.
®
The control top is activated.
Hint!
When the colours are swapped, the feedback signals are also
swapped!
Checking the Control Top
Start-up
Commissioning - Control Top with Solenoid Valve
430BAL014475EN_2
36
03.09.2021
Содержание T.VIS M-20 FDD
Страница 57: ...Appendix 430BAL014475EN_2 03 09 2021 57...
Страница 58: ......