Explanation of the items in the order code
Item in the order code
Designation
Explanation
/52
Adhesive plate (valve no.)
/UC
Certification UL/CSA
For indoor use
5.2
Technical data
Refer to the following tables for the key technical data of the control top:
Technical data: temperatures and compressed air supply
Designation
Description
Ambient temperature
-20 to +55 °C
Control air
acc. to ISO 8573-1:2010
- Solid particle content:
Quality class 6 (recommended)
Particle size max. 5 µm
Part density max. 5 mg/m3
- Water content:
Quality class 4
max. dew point +3 °C
If the unit is used at higher altitudes or at low
ambient temperatures, the dew point must be
adapted accordingly.
- Oil content:
Quality class 3
preferably oil free,
max. 1 mg oil to 1 m
3
air
Air hose
- Inch
Material PA
Outside Ø 6.35 mm
Inside Ø 4.3 mm
Control air pressure
max 8 bar, min 2 bar
Sound pressure level using sound absorber
max. 72 dB
Technical data: materials
Designation
Description
Housing
PA 12/L
Seals
FKM and NBR
Technical data
Technical data
430BAL014475EN_2
24
03.09.2021
Содержание T.VIS M-20 FDD
Страница 57: ...Appendix 430BAL014475EN_2 03 09 2021 57...