3. Perform the command “Module shutdown” on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command
“Module shutdown
” through
the
screen:
Commands 1 / Module shutdown /
Shutdown
.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
4. Disconnect the Battery on the Unit to separate by opening, if present, the “CB3 – External
Battery switch” (option) and then the “External Battery Protections”.
Press
“MUTE”
key to reset
Acoustical Alarm
.
LED ALARM
remains lit.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
NOTE !
Before performing the next procedure (5) wait 5 minutes for DC-Link Capacitors
discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage
has reached 10Vdc.
5. Disconnect the Utility supply on the Unit to separate
.
LCD display is Off
Synoptic diagram of the unit to separate
Synoptic diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest GE Service Center.