Critical Power
Modifications reserved
Page 38/91
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual
TLE Series 160 - 500 UL S2B
Code
Alarm
Description
4404
K6 CLOSING FAILURE
K6 open despite a closing command being issued.
Signaled by auxiliary contact.
The Load cannot be supplied by Automatic Bypass.
4405
K6 OPENING FAILURE
K6 closed despite an opening command being
issued. Signaled by auxiliary contact.
4406
SSM FAILURE
A faulty current has been detected in the static-
switch causing the opening of the contactor K6 for
10 seconds.
After 3 times K6 remains definitively open.
Only a GE Service Technician can reset the alarm.
4410
BYPASS UTILITY OUT OF TOLERANCE
The Utility Bypass Voltage is out of the tolerances (
±
10%).
K6 opens, synchronization with Utility is inhibited
and transfer to Utility is blocked.
4420
K3 CLOSING FAILURE
K3 open despite a closing command.
Inverter is switched OFF.
It can be restarted manually after recovery of the
alarm condition.
4421
K3 OPENING FAILURE
K3 not open despite an opening command.
Be aware the DC Capacitors could remain charged.
4520
NO INVERTER POWER
The Load supplied by Utility exceeds the Inverter
power.
The Load remains supplied by Utility until the alarm
stays ON.
4522
FAN FAILURE
The Fan Control Board indicates a malfunction of
one or more ventilators.
4530
LOAD LOCKED ON UTILITY
Load is locked on Utility because 3 transfers on
Utility have been detected in a short time (default 30
sec.).
The transfer will be free after a time defined in
parameter (default 30 sec.).
4531
LOAD ON UTILITY BY ERROR
DETECTOR
Load is transferred to Utility because the error
detector detected a disturbance on the output
voltage.
4563
EMERGENCY OFF ACTIVATED
Alarm after detection of an “EPO - Emergency Power
Off” from an external safety device connected on
Customer Interface Board.
Consequently K4, K6, K7 open, Rectifier, Inverter and
SSM are switched Off.
4570
OVERLOAD
The UPS system is in an overload condition
>
105%
on Inverter, or
>
150% on Utility.
With Utility unavailable, a sequence of “stop
operation” starts.
Time out depends on degree of overload.
4571
OVERLOAD: LOAD ON UTILITY
With Utility Bypass supply available and Load
>
115%, the Load is transferred on Utility.
Load will be transferred again automatically on
Inverter when Load
<
100%.
4581
INVERTER AND UTILITY
NOT SYNCHRONIZED
The voltages of Utility and Inverter are not
synchronized, which causes the opening of K6.
4608
ECO CONFIG FAILURE
The propagation of the eBoost / IEMi configuration
to other units in a Parallel System failed.