GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual
TLE Series 160 - 500 UL S2B
HOURS/DAY
The number of
eBoost™ Operation Mode
hours per weekday
“Monday
to
Sunday”
is displayed in the
operation mode parameter window (ceiling value).
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
•
Date and Time.
•
eBoost™
screen how many hours of eBoost™ Operation Mode have been
selected for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.
eBoost™ Operation Mode
is only possible if the UPS load exceeds a minimum
threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI
mode
.