Critical Power
Modifications reserved
Page 47/91
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual
TLE Series 160 - 500 UL S2B
IEMi SCREEN (option)
This screen is displayed only when
IEMi
Operation Mode
is available (option).
Enabled
This parameter (values
Yes/No)
enables
or disables the
IEMi Operation Mode
.
If the value is
“Yes”
and the current time
is in the interval for the current day, the
IEMi Operation Mode
.
Redundancy
Redundancy level: N+1, N+2.
Note: the redundancy level can only be updated when
IEMi Operation Mod
e is disabled (Enabled: No).
In order to enjoy the benefits of
IEMi Operation Mode
operation a system programmed for N+1
redundancy requires a parallel installation of at least three UPSs, while four UPSs are required
for
N+2 redundancy
.
The
IEMi Operation Mode
must be available on all units in a
Parallel System
.
In case of RPA Parallel System
If
IEMi Operation Mode
is currently disabled (No) and
Q1
is closed, when programming
it to enable
(Yes)
the selected configuration will automatically be propagated to all
units in the
RPA Parallel System
.
If
IEMi Operation Mode
is currently enabled
(Yes)
and
Q1
is closed, when programming
it to disable
(No)
all stand-by Inverters in the system will be switched on-line.
The activation / deactivation of IEMi Operation Mode is indicated each time in the event list. In order to
force a test of all Inverters in the system, at least 1 minute of normal operation must be programmed
during the week (the Yes/No parameter is automatically disabled if this condition is not satisfied). In
case this minimum time in normal VFI operation is not respected, the IEMi Operation Mode will be
disabled. If the value is “No”, the UPS is operating in normal VFI / double conversion mode at all times.
When the UPS is in
IEMi Operating Mode
the
IEMi
LED
is ON (green light).
NOTE !
The configuration of the activation schedule can only be updated when IEMi
Operation Mode
is disabled (Enabled: No).
DAY
For the weekdays from
“Monday to Sunday”
, the edit mode (edit day) allows to define time intervals
when the UPS is operating in
IEMi Operation Mode
. The hour is given in 24-hour format.
These intervals are defined by:
Start Time:
The hour of the day after which the
IEMi Operation Mode
is enabled.
The
IEMi Operation Mode
is enabled until the following
“Stop Time”
time is reached (the
“Stop Time”
time of the same day if this is later than the
“Start Time”
time, the
“Stop
Time”
time of the following day otherwise).
Stop Time:
The hour of the day before which the
IEMi Operation Mode
is enabled.
The
IEMi Operation Mode
is enabled starting from the preceding
“Start Time”
time (the
“Start Time”
time
of the same day if this is earlier than the
“Stop Time”
time, the
“Start Time”
time of the previous day
otherwise).
Identical times for
“Start Time”
and
“Stop Time”
maintain the existing mode only in case the previous
command was
“Start Time”
and the following command will be
“Stop Time”
.