Simon Security System
2
•
Option 19: RF Timeout set to 4 hours
•
Option 29: Control Panel Alarms set to on
•
Option 39: Siren Timeout set to 4 minutes or more
•
Option 40: Trouble Beeps set to on
•
Option 50: RF Jam Detect set to on
•
Option 53: Hardwire Siren Supervision set to on if Option 29: Control Panel
Alarms is set to off
UL 1023 & 985 24-Hour Backup
•
For 24-hour backup, the total current draw for all connected devices is limited to
25 mA (during normal standby conditions) using a 1.2 AH battery.
UL 1635 Digital Alarm Communicator System
Same as UL 1023 & 985, plus:
Note
These option settings are in
addition to UL 1023 and 985
and are required only if the
system is set up for Central
station reporting.
•
Option 12: Phone Mod 1 set to 0 or 1
•
Option 16: Auto Phone Test set to 001
•
Option 19: RF Timeout set to 4 hours
•
Option 24: AC Power Failure Report set to on
•
Option 25: CPU Low Battery Report set to on
•
Option 26: Fail to Communicate set to on
•
Option 50: RF Jam Detect set to on
Central Station Reporting
The panel has been tested with the following central station receivers using SIA and
Contact ID reporting formats:
Note
Before beginning installa-
tion, installers must verify
compatibility with the follow-
ing central station receivers.
•
Radionics D6600 Central Station Receiver
•
Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2
•
CS5000 Digital Alarm Communicator Receiver
UL Canada Listed Installations
This section describes the requirements for CUL (UL Canada) Listed installations.
Canadian Standards CSA Certified Accessories
Residential Burglary Alarm System Unit (ORD-C1023-1974)
Basic system as described for “UL 1023 Listed Installations” plus:
•
Hardwire Magnetic Contact (13-068 or 13-071) or Wireless Learn Mode Door/
Window Sensor (60-670)
•
Option 39: Siren Timeout set to 5 minutes or more
Residential Fire Warning System Control Unit (ULC-S545-M89)
Basic system as described for “UL 985 Listed Installations” plus:
•
Wireless Smoke Sensor 60-848-95 learned into sensor group 26
•
Option 39: Siren Timeout set to 5 minutes or more
•
For 24-hour backup, the total current draw for all connected devices is limited to
33 mA (during normal standby conditions) using a 1.2 AH battery.
California State Fire Marshall Listed Installations
Applied for.