RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
89
17
PMU
Synchrophasors are measured and broadcast according to the specifications
contained in IEEE C37.118, Standard for Synchrophasors for Power Systems.
For further information about the PMU, see Chapter 8: PMU.
The RPV311 is able to send up to 4 PMU in the frame of data and the configuration is
divided into three sub menus: General, Data and Communication described below.
17.1
General
This window is responsible for configuring the following settings:
<Enable> Turns the PMU streaming on and off.
The <ID> text field allows user to enter a single ID for the entire PMU streaming; the
range is of 1 to 65534.
The <Rate> scroll box allows user to select a frame transmission rate; at 60Hz the
parameters are10, 12, 15, 20, 30, and 60 fps; at 50Hz they are 10, 25 and 50Hz.
17.2
Data
The data selection is related to the groups configuration (refer to Chapter 4:
Configuration, Section 15 - Groups). Each group can configure a PMU with its specific
data and frequency.
The parameters present on the screen are:
<G
ROUP
>
this setting displays all the values related to the selected group that can be
transmitted. Each group has a particular setting for the frequency and rate of
change of frequency related to it.
The <E
NABLE
> check box allows user to enable data packet transmission.
The <ID> text field allows user to enter a single PMU transmitter ID; the range is of 1
to 65534.
<F
REQUENCY
> selects the reference frequency of PMU. It is possible to choose which
signal is used to calculate the frequency, namely: Voltage from phases A, B or C,
voltage positive sequence, current from phases A, B or C.
The <P
HASORS
>, Analog data and Digital data fields contain all the inputs configured
on the equipment. The check box allows user to select the input to evaluate
magnitudes.
The <D
ESELECT ALL
> button allows user to deselect all the magnitudes selected.
17.3
Communication
The RPV311 has two types of operation modes: Commanded; and Spontaneous.
When using the Commanded mode the RPV only transmits data when the client
requests. This mode allows up to 4 destinations of the PMU frame through the UDP
ports.
The ports the RPV311 uses to send synchrophasors are:
Содержание RPV311
Страница 2: ......
Страница 44: ......
Страница 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Страница 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Страница 104: ...Chapter 5 Operation RPV311 104 RPV311 TM EN 7 Figure 49 Records monitoring sequence harmonics flicker and SOE ...
Страница 106: ...Chapter 5 Operation RPV311 106 RPV311 TM EN 7 Figure 50 Equipment settings monitoring sequence ...
Страница 107: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 107 Figure 51 Circuit and channel settings monitoring sequence ...
Страница 108: ...Chapter 5 Operation RPV311 108 RPV311 TM EN 7 Figure 52 Relays PMU and MODBUS settings monitoring sequence ...
Страница 110: ...Chapter 5 Operation RPV311 110 RPV311 TM EN 7 Figure 53 General information monitoring sequence ...
Страница 142: ......
Страница 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Страница 152: ......
Страница 160: ......
Страница 162: ......
Страница 164: ......
Страница 204: ......
Страница 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Страница 275: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 275 Figure 143 RA331 RA332 and RA333 dimensions ...
Страница 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...