RPV311
Chapter 13
– RPV Manager
RPV311-TM-EN-7
202
4.
To ensure that the software starts with the Auto Refresh option active,
check the box "Auto Polling on Init" on the Configuration>Polling menu;
The refresh action also happens during the:
Start of application execution;
Change in list of substations;
Change in the equipment list.
After communication with the equipment, the software checks if any information was
changed and updates the information as follows:
Interface: System Monitor equipment tree tab and equipment lists in the
other tabs;
Database;
Information of the Transmission Line configurations for each device;
Name of the directory where the new records will be downloaded.
2.4.2
Polling
The polling routine is responsible for performing the automatic download of records
from each equipment.
Configure the Auto Polling as follows:
1.
For each equipment if you want to have Auto Polling functionality, "Enable
Auto COMTRADE Download " should be enabled.
2.
To set the update interval, the field "Auto Polling Interval" must be changed
in the Polling configuration screen.
3.
To activate or deactivate the Auto Polling, access the menu Polling Auto, to
activate, and Polling > Manual, to disable.
4.
To ensure that the software starts with the Auto option active Polling, select
the field "Auto Polling on Init" on the Polling configuration screen
5.
COMTRADES records will only be downloaded that are younger than the
period entered in the field “Polling COMTRADE Acts ", in Polling configuration
screen,
6.
Only the types of COMTRADE records configured through the fields "Retrieve
..." in the Polling configuration screen of will be downloaded.
7.
To run the fault location algorithm automatically after downloading a
COMTRADE record, select the field "Automatic Fault Location", in Polling
configuration screen.
8.
Once everything is configured, the records will be downloaded to the
directory "COMTRADE Directory "/Records.
When the Auto Polling is set to on it will run during the following occasion:
1.
At system start up;
2.
When closing the
Device
window.
Enable Automatic Polling by clicking the menu Polling>Auto;
If the Auto Polling is active, each time interval is set in "Auto Polling COMTRADE
Interval ".
Содержание RPV311
Страница 2: ......
Страница 44: ......
Страница 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Страница 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Страница 104: ...Chapter 5 Operation RPV311 104 RPV311 TM EN 7 Figure 49 Records monitoring sequence harmonics flicker and SOE ...
Страница 106: ...Chapter 5 Operation RPV311 106 RPV311 TM EN 7 Figure 50 Equipment settings monitoring sequence ...
Страница 107: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 107 Figure 51 Circuit and channel settings monitoring sequence ...
Страница 108: ...Chapter 5 Operation RPV311 108 RPV311 TM EN 7 Figure 52 Relays PMU and MODBUS settings monitoring sequence ...
Страница 110: ...Chapter 5 Operation RPV311 110 RPV311 TM EN 7 Figure 53 General information monitoring sequence ...
Страница 142: ......
Страница 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Страница 152: ......
Страница 160: ......
Страница 162: ......
Страница 164: ......
Страница 204: ......
Страница 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Страница 275: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 275 Figure 143 RA331 RA332 and RA333 dimensions ...
Страница 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...