5-130
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-59: User-programmable pushbutton logic (Sheet 2 of 2)
5.3.16 Flex state parameters
SETTINGS
PRODUCT SETUP
FLEX STATE PARAMETERS
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256
state bits.
FLEX STATE
PARAMETERS
PARAMETER 1:
Off
Range: FlexLogic operand
PARAMETER 256:
Off
Range: FlexLogic operand