7-12
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
TARGETS MENU
CHAPTER 7: COMMANDS AND TARGETS
7
•
Latched target message
: No.
•
Description of problem
: One or more RxGOOSE messages are not being received.
•
How often the test is performed
: The self-test is activated when no message is received within the expected time
interval, which is the time-to-live time in the previous message. This time can be from milliseconds to minutes.
•
What to do
: Check GOOSE setup.
•
Latched target message
: No.
•
Description of problem
: The second line of this self-test error indicates the problem with the PMU Aggregator.
•
How often the test is performed
: Each time a PMU’s related settings is changed.
•
What to do
: Correct the problem indicated in the second line or contact the factory.
•
Latched target message
: Yes.
•
Description of problem
: The ambient temperature is greater than the maximum operating temperature (+80°C).
•
How often the test is performed
: Every hour.
•
What to do
: Remove the N60 from service and install in a location that meets operating temperature standards.
•
Latched target message
: Yes.
•
Description of problem
: Abnormal restart from modules being removed or inserted while the N60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
•
How often the test is performed
: Event driven.
•
What to do
: Contact the factory.
•
Latched target message
: Yes.
•
Description of problem
: A link loss detection on an Ethernet port. The link loss is due to unplugging the cable or the
switch port being down.
•
How often the test is performed
:
•
What to do
: Check the connection.
•
Latched target message
: Yes.
RxGOOSE FAIL:
Missing messages
AGGREGATOR ERROR:
TEMP MONITOR:
OVER TEMPERATURE
UNEXPECTED RESTART:
Press “RESET” key
FIRST ETHERNET FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
WRONG TRANSCEIVER