CHAPTER 5: SETTINGS
SYSTEM SETUP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-169
5
Figure 5-91: CFG-2 based configuration solution
5.5.7.7 Modification of SYNC word in CFG-2 for TR 90-5 data sets
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets).
In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which is set presently to 2) is set as follows:
5.5.7.8 Settings
The PMU settings are organized as follows.
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PHASOR MEASUREMENT UNIT 1(6)
5.5.7.9 Basic configuration
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
BASIC CONFIGURATION
PMU 1(6)
Value (decimal)
Number of ASDUs
11
1
12
2
13
3
14
4
PHASOR MEASUREMENT
UNIT 1
PMU 1 BASIC
CONFIGURATION
See below
PMU 1
CALIBRATION
PMU 1
TRIGGERING
PMU 1
RECORDING
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
PMU 1 IDCODE:
1
Range: 1 to 65534 in steps of 1
PMU 1 STN:
GE-UR-PMU
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
Содержание N60
Страница 10: ...x N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 650: ...iv N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 666: ...xvi N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM INSTRUCTION MANUAL INDEX ...