5-74
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Note that a dataset can hold at most 64 basic data attribute values, and that a single structured data object or attribute
can contain multiple basic data attribute values. UR Setup software does not allow more that 64 basic data attribute
values to be entered, in which case the last several members settings cannot be changed from End of List.
Note that the publisher's name alone does not contain all the information required for subscription, additional publisher
information model information is stored elsewhere. For this reason, manual entry of the name is not supported.
RxGOOSE inputs
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean value received by a specified RxGOOSE to a FlexLogic
operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) value to four FlexLogic
operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a specified
FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the RxGOOSE
connectivity is lost. Other types of values can be present in subscribed GOOSE messages, but cannot be converted to
operands. An RxGOOSE Input that is mapped to a value that in the GOOSE message is a child of a data object reverts to its
configured default value while the Quality value in that data object is invalid, and also while the Quality value is test and
this relay's
TEST MODE FUNCTION
setting is other than Forcible or Isolated.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible in the UR Setup software. See the UR Family Communications Guide for more
information on GGIO3.
RxGOOSE Boolean inputs
Navigate to
Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Boolean Inputs
.
The number of RxGOOSE Boolean (remote inputs) is 256.
There are
Add IED
and
Remove IED
buttons. The
Add IED
button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the
user select the ones to add. The figure shows a selection being made by importing a CID file using the
Add IED
function.