6.4.15 Transducer inputs and outputs
ACTUAL VALUES
METERING
TRANSDUCER I/O DCMA INPUTS
DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES
METERING
TRANSDUCER I/O RTD INPUTS
RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6.5 Records
6.5.1 User-programmable fault reports
ACTUAL VALUES
RECORDS
USER-PROGRAMMABLE FAULT REPORTS
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for information on this feature.
6.5.2 Event records
6.5.2.1 Enhanced and standard front panels
ACTUAL VALUES
RECORDS
EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the
COMMANDS
CLEAR RECORDS
menu for clearing event records.
DCMA INPUT xx
DCMA INPUT xx
0.000 mA
RTD INPUT xx
RTD INPUT xx
-50 °C
USER-PROGRAMMABLE
FAULT REPORTS
NEWEST RECORD
NUMBER: 0
LAST CLEARED DATE:
2002/8/11 14:23:57
LAST REPORT DATE:
2002/10/09 08:25:27
EVENT RECORDS
EVENT: XXX
XXX
Date and time stamps
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED