EPM 2200 POWER METER – INSTRUCTION MANUAL
CONFIGURING COM OPTION B: BACNET MS/TP WITH MODBUS TCP/IP CHAPTER 7: COM OPTION B: BACNET MS/TP WITH MODBUS TCP/IP
5.
Click
OK
. You will see the BACnet MS/TP Interface webpage, shown below.
6.
Click
TCP/IP
and
BACnet Settings
on the left side of the webpage to see the page
shown below. Use this page to change the default IP address (10.0.0.1) to an IP address
in the same subnet as your Network. Contact your System Administrator if you are
unsure of the correct address to use.
You can also change the following fields:
•
Network Mask
- the subnet mask. The default is 255.255.255.0.
•
Default Gateway
- the IP address of the gateway. The default is 10.0.0.224.
•
BACnet Device Number
- a numeric code used to identify the meter. This number
is auto-generated from the MAC address.
•
BACnet Device Name
- field for the device name, which can be up to 63
characters in length.
•
BACnet Device Description
- optional field where you can enter a description of
up to 63 characters which will be added as a prefix in the name of all registers
representing the meter’s BACnet objects.