CHAPTER 6: USING THE METER
PROGRAMMING USING THE FACEPLATE
EPM 2200 POWER METER – INSTRUCTION MANUAL
6–11
4.
Press
ENTER
again to select the to
Pt-S
(PT scaling) value.
The
Pt-S
value can be “1”, “10”, or “100”. Refer to
Programming the Configuration Mode
Screens
on page 7–7 for instructions on changing values.
Example settings for the
Pt-n
,
Pt-d
, and
Pt-S
values are shown below:
5.
Press
ENTER
to scroll through the other
CFG
parameters.
6.
Press
DOWN
or
RIGHT
to display the password screen (see
Reset Mode
on
page 7–4 for details).
7.
Press
MENU
to return to the Main Configuration Menu.
NOTE
Note
Pt-n
and
Pt-S
are dictated by primary voltage.
Pt-d
is secondary voltage.
6.1.11 Configuring the Connection (Cnct) Setting
Use the following procedure to program the connection (
Cnct
) setting.
1.
Push the
DOWN
Button to scroll through the Configuration Mode parameters:
Scroll, CT, PT, Connection (Cnct), and Port. The "active" parameter is in the A
screen and is flashing
277/277 Volts: Pt-n
value is 277, Pt-d value is 277,
Pt-Multiplier
is 1
14400/120 Volts:
Pt-n
value is 1440, Pt-d value is 120,
Pt-S
value is 10
138000/69 Volts:
Pt-n
value is 1380, Pt-d value is 69,
Pt-S
value is 100
345000/115 Volts:
Pt-n
value is 3450, Pt-d value is 115,
Pt-S
value is 100
345000/69 Volts:
Pt-n
value is 345, Pt-d value is 69,
Pt-S
value is 1000
Содержание Multilin EPM 2200
Страница 30: ...2 10 EPM 2200 POWER METER INSTRUCTION MANUAL ACCURACY CHAPTER 2 OVERVIEW AND SPECIFICATIONS ...
Страница 54: ...4 20 EPM 2200 POWER METER INSTRUCTION MANUAL ELECTRICAL CONNECTION DIAGRAMS CHAPTER 4 ELECTRICAL INSTALLATION ...
Страница 82: ...6 24 EPM 2200 POWER METER INSTRUCTION MANUAL GE COMMUNICATOR PROGRAMMING OVERVIEW CHAPTER 6 USING THE METER ...
Страница 104: ...A 6 EPM 2200 POWER METER INSTRUCTION MANUAL NAVIGATION MAPS SHEETS 1 TO 4 APPENDIX A EPM 2200 NAVIGATION MAPS ...