CHAPTER 4: ELECTRICAL INSTALLATION
ELECTRICAL CONNECTION DIAGRAMS
EPM 2200 POWER METER – INSTRUCTION MANUAL
4–19
4.2.11 (10) Current-Only Measurement (Single-Phase)
For this wiring type, select
3 EL WYE
(3 Element Wye) in the meter programming setup.
Figure 4-16: Current-Only Measurement (Single-Phase)
Note
Even if the meter is used only for current measurement, the unit requires a AN volts
reference. Please ensure that the voltage input is attached to the meter. AC control power
can be used to provide the reference signal.
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
L(+)
Power
Supply
Connection
N(-)
L(+)
GND
N(-)
Vref
Va
Vb
Vc
LINE
LOAD
CT
Shorting
Block
FUSE
3A
FUSE
0.1A
20VAC
Minimum
N
N
A
A