![GE Multilin EPM 2200 Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/ge/multilin-epm-2200/multilin-epm-2200_instruction-manual_128409026.webp)
2–6
EPM 2200 POWER METER – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: OVERVIEW AND SPECIFICATIONS
WH PULSE
KYZ output contacts (and infrared LED light pulses through face plate)
:
Pulse Width: ....................................40ms
Full Scale Frequency: ..................6Hz
Contact type: ..................................Solid State – SPDT (NO – C – NC)
Relay type: .......................................Solid state
Peak switching voltage: .............DC ±350V
Continuous load current: ..........120mA
Peak load current: ........................350mA for 10ms
On resistance, max.: ....................35
Ω
Leakage current: ...........................1
μ
A@350V
Isolation: ...........................................AC 3750V
Reset State: ......................................(NC - C) Closed; (NO - C) Open
Infrared LED
:
Peak Spectral Wavelength: ......940nm
Reset State: ......................................Off
Figure 2-1: Internal Schematic (De-energized State)