CHAPTER 6: USING THE METER
PROGRAMMING USING THE FACEPLATE
EPM 2200 POWER METER – INSTRUCTION MANUAL
6–13
The following parameters can be configured through the
POrt
menu
•
The meter
Address
(
Adr
, a 3-digit number).
•
The
Baud Rate
(
bAUd
). Select from “9600”, “19.2”, “38.4”, and
“57.6” for 9600, 19200, 38400, and 57600 kbps, respectively.
•
The
Communications Protocol
(
Prot
). Select “rtU” for Modbus
RTU, and “ASCI” for Modbus ASCII.
• The first
POrt
screen is
Meter
(
Adr
). The current address appears on the screen.
Select a three-digit number for the address.
Refer to
Programming the Configuration Mode Screens
above for details on changing
values.
• The next
POrt
screen is the baud rate (
bAUd
). The current baud rate is displayed on
the “B” screen. Refer to
Programming the Configuration Mode Screens
above for
details on changing values. The possible baud rate screens are shown below.
• The final
POrt
screen is the
Communications Protocol
(
Prot
).
The current protocol is displayed on the “B” screen.
Address 005