EPM 2200 POWER METER – INSTRUCTION MANUAL
5–1
EPM 2200 Power Meter
Chapter 5: Com Option S: Modbus/
KYZ output
GE
Grid Solutions
Com Option S: Modbus/KYZ output
The Communication Options available for the EPM 2200 are connected and used in
different ways.
•
Com Option S: Modbus/KYZ output is explained here in Chapter 5.
•
Com Option B: BACnet MS/TP with Modbus TCP/IP Internet is explained in Chapter 7 on
page 7-1.
5.1
Connecting to the RS485/KYZ Output Port
The EPM 2200 Meter with Communications Option S provides a combination RS485 and a
KYZ Pulse Output for pulsing energy values. The RS485 / KYZ Combo is located on the
terminal section of the meter, and provides RS485 communication speaking Modbus ASCII
and Modbus RTU protocols.
The EPM 2200 meter’s RS485 port can be programmed with the buttons on the face of the
meter or by using GE Communicator software.
The standard RS485 Port Settings are as follows:
•
Address: 001 to 247
•
Baud Rate: 9600, 19200, 38400 or 57600
•
Protocol: Modbus RTU, Modbus ASCII
Details of changing the RS485 port settings are given in Chapter 6, using the faceplate: 6.1
Programming Using the Faceplate
on page 6–1, and using the GE Communicator software:
6.4.2
How to Connect Using GE Communicator Software
on page 6–17.
Содержание Multilin EPM 2200
Страница 30: ...2 10 EPM 2200 POWER METER INSTRUCTION MANUAL ACCURACY CHAPTER 2 OVERVIEW AND SPECIFICATIONS ...
Страница 54: ...4 20 EPM 2200 POWER METER INSTRUCTION MANUAL ELECTRICAL CONNECTION DIAGRAMS CHAPTER 4 ELECTRICAL INSTALLATION ...
Страница 82: ...6 24 EPM 2200 POWER METER INSTRUCTION MANUAL GE COMMUNICATOR PROGRAMMING OVERVIEW CHAPTER 6 USING THE METER ...
Страница 104: ...A 6 EPM 2200 POWER METER INSTRUCTION MANUAL NAVIGATION MAPS SHEETS 1 TO 4 APPENDIX A EPM 2200 NAVIGATION MAPS ...