2–4
EPM 2200 POWER METER – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: OVERVIEW AND SPECIFICATIONS
window demand is a fixed window demand that moves for a user-specified subinterval
period. For example, a 15-minute demand using 3 subintervals and providing a new
demand reading every 5 minutes, based on the last 15 minutes.
Utility demand features can be used to calculate kW, kVAR, kVA and PF readings. All other
parameters offer maximum and minimum capability over the user-selectable averaging
period. Voltage provides an instantaneous maximum and minimum reading which
displays the highest surge and lowest sag seen by the meter.
2.2
Specifications
POWER SUPPLY
Range:.................................................Universal, (90 to 265) VAC @50/60Hz
Power consumption:....................5 VA, 3.5 W
VOLTAGE INPUTS (MEASUREMENT CATEGORY III)
Range:.................................................Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L
Supported hookups:.....................3-element Wye, 2.5-element Wye,
2-element Delta, 4-wire Delta
Input impedance: ..........................1 MOhm/phase
Burden: ...............................................0.0144 VA/phase at 120 Volts
Pickup voltage:................................10 V AC
Connection: ......................................Screw terminal
Maximum input wire gauge: ...AWG #12 / 2.5 mm
2
Fault withstand:..............................Meets IEEE C37.90.1
Reading: .............................................Programmable full-scale to any PT ratio
CURRENT INPUTS
Class 10:.............................................5 A nominal, 10 A maximum
Burden: ...............................................0.005 VA per phase maximum at 11 A
Pickup current:................................0.1% of nominal
Connections:....................................O or U lug;
Pass-through wire, 0.177" / 4.5 mm maximum diameter
Quick connect, 0.25" male tab
Fault Withstand (at 23°C):..........100 A / 10 seconds, 300 A / 3 seconds, 500 A / 1 second
Reading: .............................................Programmable full-scale to any CT ratio
ISOLATION
All Inputs and Outputs are galvanically isolated to 2500 V AC
ENVIRONMENTAL
Storage:..............................................–20 to 70°C
Operating: .........................................-20 to 70°C
Humidity:...........................................up to 95% RH, non-condensing
Faceplate rating:............................NEMA 12 (water resistant), mounting gasket included
METER ENCLOSURE ENVIRONMENTAL
Storage:..............................................–20 to 70°C
Operating: .........................................-10 to 50°C
Humidity:...........................................up to 95% RH, non-condensing
Faceplate rating:............................NEMA 1 (Indoor Use)
Pollution degree .............................II
Overvoltage Category.................III (this product is designed for indoor use only)
MEASUREMENT METHODS
Voltage and current: ....................True RMS
Power:.................................................Sampling at 400+ samples/cycle on all channels measured; readings
simultaneously
A/D conversion: ..............................6 simultaneous 24-bit analog-to-digital converters
Содержание Multilin EPM 2200
Страница 30: ...2 10 EPM 2200 POWER METER INSTRUCTION MANUAL ACCURACY CHAPTER 2 OVERVIEW AND SPECIFICATIONS ...
Страница 54: ...4 20 EPM 2200 POWER METER INSTRUCTION MANUAL ELECTRICAL CONNECTION DIAGRAMS CHAPTER 4 ELECTRICAL INSTALLATION ...
Страница 82: ...6 24 EPM 2200 POWER METER INSTRUCTION MANUAL GE COMMUNICATOR PROGRAMMING OVERVIEW CHAPTER 6 USING THE METER ...
Страница 104: ...A 6 EPM 2200 POWER METER INSTRUCTION MANUAL NAVIGATION MAPS SHEETS 1 TO 4 APPENDIX A EPM 2200 NAVIGATION MAPS ...