GE_UPS_ISG_LPS_3UL_20K_30K_2US_V010.docx
Installation Guide
LP33 Series 20 & 30 UL S2
4.9
ELECTRICAL CONNECTIONS
WARNING !
The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY. Refer to the “
Safety Rules - Installation
” described on page 6.
4.9.1
Common input utility
Fig. 4.9.1-1 Common input utility
Common input utility
The UPS delivered in standard
version has
common input utility
.
Only one input line
(F1)
supplies
both
rectifier
and
bypass
input
terminals.
Bear in mind that when the utility
fuses are opened there is a supply
failure to the
rectifier
as well as to
the
automatic bypass
and manual
bypass
.
Fig. 4.9.1-2 Terminals for common input mains
X1 Utility 1 - Input utility connection
L1
= Rec Bypass Phase A
L2
= Rec Bypass Phase B
L3
= Rec Bypass Phase C
N1
= Utility Neutral
PE
= Main Ground
X3 Load - Output load connection
L1
= Load Phase L1
L2
= Load Phase L2
L3
= Load Phase L3
N2
= Load Neutral
PE
= Load Ground
Max. rating
X1
,
X2
and
X3
terminals:
LP33 Series 30
1/0 AWG
(70mm
2
)
LP33 Series 40
4/0 AWG
(95mm
2
)
Connect wire to the
Terminals
using appropriate tools and appropriate torque shown in
Section 4.8.1
.
NOTE !
For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals
N1
and
N2
are connected together.
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.
Load
X3
L1
L2
L3
N2
PE
LPS33U
_040-08
0_Conn
ection c
ommon_
02US
Utility 1
X4
Battery
X1
L1-1
L2-1
L3-1
N1
PE
-
0
+
PE