Operating Temperature*
32°F to 122°F
(0°C to 50°C)
Operating Humidity
10% to 85% RH (non-condensing) at less than
50°C; maximum 50% RH at greater than 50°C
Storage Temperature*
-4 to 140°F
-20 to 60°C
Storage Humidity
10% to 85% RH (non-condensing) at less than
50°C; maximum 50% RH at greater than 50°C
NEMA Rating
4 and 4x (NEMA 4 is approximately equivalent to
IP66; visit www.nema.org)
Operational Vibration
IEC 60068-2-6
10
–57Hz, 0.012” peak to peak displacement
57
–500Hz, 1.0g acceleration
Operational Shock
IEC 60068-2-27
15g, 11ms (sine wave)
*
Rated temperature limits refer to the ambient air temperature immediately
surrounding (less than 3” or 7.6 cm) the QuickPanel. Additional provisions for
remaining within the stated limits must be considered where additional, external
thermal loads are imposed on the QuickPanel. These could include large heat
producing motor drives, or power supplies in the same cabinet or in outdoor
applications involving direct sun exposure.
Battery
Type
Panasonic BR2032 (3V, 190mAh, lithium)
Approximate life
5 years
Calendar/Clock
Resolution
1 second
Accuracy
±2 to 3 minutes per month
Retention
Life of battery