3-4
15" QuickPanel* View & QuickPanel Control Loaded Color TFT
– December 2011
GFK-2402D
3
Installation Using Mounting Clamps
To secure the QuickPanel View/Control to a panel, use the 16 included
mounting clamps. They hook into openings located on the top, bottom, and
sides of the housing.
1. Insert the unit into the panel cutout (without a CF card in the CF port).
Note:
To avoid damage to the unit or associated components, do not fit the
unit into this cutout with a CF card inserted in the port, with any cables
connected, or with the power plug inserted in the socket.
2. Insert the hook of each mounting clamp into the housing openings as
shown below.
3. Ensure that the gasket is properly seated in the bezel channel and firmly
tighten the clamp screws.
Note:
The torque range for the mounting clamp screws is
2.6
–4.4 inch/lbs (0.3–0.5 Nm).
The mounting clamps
hold the unit in place by
tension. No drilling is
required.
Caution
Do not damage the gasket attached to the back of the QuickPanel. This gasket
provides the protection from ingress of water, dust, and other potentially
harmful contaminants.
Too many installations using the same gasket may cause gasket “set” and
degradation of the seal. Limit repeated insertions or removals of the unit and
retightening of the mounting clips. To ensure the necessary IP rating is
maintained, always use a new gasket. Replacement gaskets may be ordered
using part number IC754ACC15GAS.