GFK-2402D
Chapter 3 Installation
3-5
3
Connecting a DC Power Supply
1. Using the three screw terminals shown in the following diagram, attach
a 24VDC, 48W power supply to the plug supplied with the QuickPanel
View/Control using 12 to 18 AWG. For frame ground, use shortest
length 14 AWG wire to ground.
2. Insert the plug into the power supply socket and securely tighten the
attaching screws.
Note:
The torque range for the attaching screws is 4
–6 inch/lbs
(0.45
–0.68 Nm).
Bottom View
Power Supply Plug