66
• Application diagrams
8.10
Energy Save, Slow Speed or Reset
Notes
:
•
Switch D can be used as an
Energy
Save/Slow Speed/ Reset
, as
programmed in I/O
Programming
Parameters
•
Energy Save
or
Slow Speed
functions require a maintained
contact to operate.
•
Reset
function requires a momentary
contact to operate
•
The drawing shows Control Supply and
Control Input from the same source.
Refer to section
and Control Input from separate
sources.
8.11
Slow Speed and Slow Speed Reverse
•
For Slow speed operation:
o
Program Input terminal 7 as
Slow Speed
. Refer to section
o
Connect Control Input voltage
to terminal 7 and start the soft
starter. Motor will run at
Slow
Speed
.
•
For Slow speed reverse operation:
o
Program Input terminal 7 as
Slow Speed
. Refer to section
o
Program Input terminal 8 as
Slow Speed Reverse
.
Refer to section
o
Connect Control Input voltage
to terminal 7 and start the soft
starter. Motor will run at
Slow
Speed
. When Control Input
voltage is connected to
terminal 8 motor will stop and
Slow Speed Reverse
.
o
If Control Input voltage is
connected to terminal 8 before
start command, motor will run
at
Slow Speed Reverse
when the start command is
initiated.
•
The drawing shows Control Supply
and Control Input from the same
source. Refer to section
Supply and Control Input from
separate sources.
Содержание ASTAT XT QT 0008U Series
Страница 1: ...GE Consumer Industrial ASTAT XT User Manual...
Страница 17: ...17 Technical Specifications 3 4 I O Wiring...
Страница 123: ...Ed 15 03 09 Copyright GE Power Controls 2009...