40
• Control Keypad
4.7.8
I/O Settings Parameters
– Page 7
Function &
Default
Range
Unit
Description
PROG. Input # 7
Reset
Reset;
Slow Speed;
Energy Saving
Sets the terminal 7 function
Refer to section
4.7.8.1 on page 41.
PROG. Input # 8
Dual Settings
Dual Settings;
Slow SPD
Reverse;
Reset;
Sets the terminal 8 function
Refer to section
4.7.8.1 on page 41.
PROG. Fault Relay
At Fault Close
At Fault Close,
At Fault Open
Sets the Fault Relay mode of operation.
When configured to
At Fault Close
the internal
relay is energized upon fault.
When configured to
At Fault Open
the relay is de-
energized upon fault. In this mode, while normal
operation, the fault relay is energized.
Relay will also de-energize upon control power outage.
Relay ON Delay
0 SEC.
0 – 3600
sec.
Sets ASTAT-XT’s Immediate Relay (RUN relay)
ON delay time.
Relay OFF Delay
0 SEC.
0 – 3600
sec.
Sets ASTAT-XT’s Immediate Relay (RUN relay) OFF delay
time.
Analog Output
I, 0...200% OF Im
I, 0...200% OF Im
Sets Analog Output mode of operation.
The dip switch settings on the analog card define full
scale as either 20mA or 10V. Refer to section
page 51 for more details.
The full scale of the analog card is related to 200% of
Motor Current
(2x <
rated motor current
>).
Store Settings
I/O Settings
Same
as
Store Settings Main Settings
41
Displays in MINIMIZED MODE and MAXIMIZED MODE.