32
• Control Keypad
Function &
Default
Range
Unit
Description
Max. Start Time
30 SEC.
1-60
sec.
Sets Maximum Start Time
The maximum allowable start time, from the start signal to the
end of the acceleration process. If voltage/speed does not reach
nominal during
Max. Start Time
then ASTAT-XT will trip the
motor and create a fault. The LCD will display the
Long Start
Time
fault message.
For example, this can occur when the
Current Limit
setting
is too low.
Notes:
•
When
Overload Class
is set to
NEMA Class 10 Max.
Start Time
can be set to 15 seconds maximum.
•
When
Overload Class
is set to
IEC Class 10
or
NEMA
Class 20
Max. Start Time
can be set to 30 seconds
maximum.
•
When
Overload Class
is set to
IEC Class 20
or
NEMA
Class 30 Max. Start Time
can be set to 60 seconds
maximum with limitation automatically calculated by the soft
starter.
Number of Starts
10
1-10, OFF
Sets Number of Starts permitted during Duty Cycle Time (see
below).
Limits the
Number of Starts
during the period of time
defined by
Duty Cycle Time
.
If you try to start even one more time within that period the
START Lockout
period will take effect.
Duty Cycle Time
30 Min.
1–60
min.
Sets Duty Cycle Time during which Number of Starts is counted.
During the
START Lockout
period the
Wait before RST
XX Min
message will be displayed.
Start Lockout
15 Min.
1–60
min.
Sets START Lockout time during which starting is disabled after
Too Many Starts
trip.
EOR Relay Delay
5 Sec.
0-120
sec.
Sets the time delay for the End of Ramp relay to close.
End of Ramp relay can signal that the motor is at its full speed
which can be used for closing the bypass contactor and for
loading the motor.
Store Settings
Start Settings
Same
as
Store Settings Main Settings
4.7.3.1
Soft Start Parameters
The ASTAT-XT incorporates five starting curves to enable you to select a suitable torque curve.
Soft Start Curve 0
– Standard curve (Default). This curve is the most suitable curve for preventing prolonged
starting and motor overheating.
Note:
When ASTAT-XT is connected in
DELTA Conf
., the ASTAT-XT will always use
Curve 0
regardless of the curve
defined.
Содержание ASTAT XT QT 0008U Series
Страница 1: ...GE Consumer Industrial ASTAT XT User Manual...
Страница 17: ...17 Technical Specifications 3 4 I O Wiring...
Страница 123: ...Ed 15 03 09 Copyright GE Power Controls 2009...