90
•
Appendix A - MODBUS RTU Protocol
Parameter
#
(3x)
#
(4x)
Comment
Last Fault
24
280
# of the fault that caused trip.
# Fault
01
Over Temperature
02
Short Cir. Curr.
03
Overload
04
Under Current
05
Under Voltage
06
Over Voltage
07
Phase Loss
08
Phase Sequence
09
Shorted Scr
10
Long Start Time
11
Slow Speed Time
12
Wrong Connection
13
External Fault
14
Wrong Parameters
15
EMI/RFI Fault
16
Too Many Starts
17
Reserved
18 Thermistor.
19 Frequency
Motor FLT Current
25
281
Current at trip time, % of Im.
Reserved
26..36
282..292
Thermal Capacity
37
293
Reserved
38..108
293..364
Actual_Data_Group
109..128 365..384
Group of 20 actual parameters selected by
parameter settings 90..109
Example 1:
To read actual parameters 2 and 3 (Motor Current and Mains Voltage Actual Parameters, Addressed as 1 and 2) of
ASTAT-XT # 18 (its SERIAL LINK NO. = 18), the host computer should send following frame:
Another Possibility
(Modbus Plus users)
byte
1:
Serial
Link
No.
($12)
($12)
byte
2:
Function ($04)
($03)
byte
3:
Starting
Address
High
($00)
($01)
byte
4:
Starting
Address
Low
($01)
($01)
byte
5:
No.
of
Points
High
($00)
($00)
byte
6:
No.
of
Points
Low
($02)
($02)
byte
7:
CRC_Low
($XX)
($XX)
byte 8: CRC_High
($XX)
($XX)
The ASTAT-XT response, when Current = 400 % of Im, and Voltage = 420V, is:
byte
1:Serial
Link
No.
($12)
($12)
byte
2:
Function ($04)
($03)
byte
3:
Byte
Count
($04)
($04)
byte 4: Data High, parameter 2
($01)
(400)
($01)
byte
5:
Data
Low,
parameter
2
($90)
($90)
byte 6: Data High, parameter 3
($01)
(420)
($01)
byte
7:
Data
Low,
parameter
3
($A4)
($A4)
byte
8:
CRC_Low
($XX)
($XX)
byte 9: CRC_High
($XX)
($XX)
Note:
$XX indicates Hexadecimal byte.