59
• Trouble Shooting
7.
TROUBLE SHOOTING
Upon fault – motor stops, the
Fault
LED lights and Fault Relay chances position. The LCD shows TRIP: < fault
description>. (for example:
Trip: Undercurrent
).
Storage Error
Storage Error displays in case of a failure in parameter storing.
Wait 3 seconds and try to store again.
If does not help, load the default parameters of the ASTAT-XT and re-program all
parameters.
To obtain default parameters refer to section
Access Locked
Avoids parameter changing when dip switch # 8 –Software Lock is set to ON.
If parameter changing is required verify that dip switch #8 is set to OFF.
For Dip switch #8 setting refer to section
Thermistor Trip
Trips the ASTAT-XT when the motor thermistor resistance decreases below trip level
set.
Check resistance of the thermistor and cables; Check motor temperature near
thermistor location.
For
Thermistor Trip
protection setting refer to section
Too Many Starts
Trips the ASTAT-XT if the
number of starts
, during
Duty Cycle Time
exceeds the preset number.
Wait until motor and ASTAT-XT cool down – according to
Number Of Starts
,
Duty Cycle Time
and
Start Lockout settings
. Refer to section
page 32.
Long Start Time
Trips the ASTAT-XT if output voltage does not reach nominal at the preset
Max.
Start time.
Check
Starter Current
and
Max. Start Time
settings. Increase
Starting
Voltage, Current Limit
&
Max. Start Time
or decrease
Ramp UP
Time
as necessary.
For
start Settings Parameters
refer to section
O/C JAM Fault
Trips the ASTAT-XT when:
•
Instantaneously when current exceeds 8.5 x ASTAT-XT Current
•
During starting when current exceeds 8.5 x Motor Current
•
During running when current exceeds 200-850% of Motor Current.
O/C JAM Fault
has a programmable delay of 0-5 seconds where the ASTAT-XT
detects the fault and does not trip before time delay has elapsed (delay is overriden
when current reaches 8.5 x ASTAT-XT Current).
Check that motor is not stalled or jammed.
Check
Motor Current and
Starter Current
settings.
Check motor and cable connections.
Perform a “Megger” test to verify motor and cable’s condition.
For protection parameters settings refer to section
CAUTION
Check that “Megger” maximum voltage is no more than 500V!
Disconnect terminal 21 before performing a “Megger” test.
Overload
Trips the ASTAT-XT when current exceeds the Overload Trip level and the thermal
register has filled up.
Check
Motor Current
,
Starter Current
settings and overload settings and
check motor current, then wait at least 15 minutes to let the motor and ASTAT-XT
cool down before restarting.
For protection parameters settings refer to section
Содержание ASTAT XT QT 0008U Series
Страница 1: ...GE Consumer Industrial ASTAT XT User Manual...
Страница 17: ...17 Technical Specifications 3 4 I O Wiring...
Страница 123: ...Ed 15 03 09 Copyright GE Power Controls 2009...