38
• Control Keypad
4.7.7
Fault Settings
– Page 6
Function &
Default
Range
Unit
Description
Phase Loss
Enabled
Enabled
Sets Phase Loss trip
Phase Loss protection trips the ASTAT-XT when 1 or 2 phases
are missing.
Notes:
If ASTAT-XT trips on
Phase Loss
do the following:
(1)
In cases where the current transformers are connected
externally (ASTAT-XT 950-1400A models), verify that that
the current transformers are not grounded. Each current
transformer is connected with its 2 wires only and these
wires are not grounded externally.
(2)
Check phase voltages related to terminal 21 even if
terminal 21 is not connected. Verify that phase voltages
are within the required range of line to neutral voltages.
(3)
Verify that terminal 21 is connected correctly. For terminal
21 connection refer to section
(4)
If terminal 21 is connected correctly, disconnect terminal
21 and try to start when terminal 21 is disconnected.
(5)
If all previous actions are do not solve the problem and
the you are sure that no real phase loss exists, you can set
Phase Loss protection to
Disable
.
This situation can occur in rare cases when there is no real
fault but the ASTAT-XT recognizes unusual behaviour like
when Total Harmonic Distortion in Voltage (THDV) in the
network is high.
(6)
If this is a true case of
Phase Loss
then after setting
Phase Loss
protection to
Disable
the motor will
single phase and most likely be tripped by the over load
protection mechanism.
(7)
Phase loss
might not be detected in motor operating
under a light load.
WARNING
Do not set
Phase Loss
to
Disable
unless it is found to be
necessary in the field!
Phase Sequence
Disabled
Enabled/
Disabled
Sets Phase Sequence trip
When ASTAT-XT is connected in
DELTA Conf.
you can not
set
Phase Sequence
protection to
Disabled
.
Auto Reset
Disabled
Enabled/
Disabled
Sets ASTAT-XT’s Auto Reset mode of operation.
The ASTAT-XT can be automatically reset for
Undervoltage
and
Phase Loss
faults.
4.7.2 on page 27 for details on setting
Undervoltage
protection.
To start the motor after
Undervoltage
and
Phase Loss
faults have been cleared, remove the START signal and
recommence the signal.
Auto Reset function has a non-programmable time delay of 60
seconds.
Note:
The
Auto Reset
operation is limited to 10 operations.
39
Displays in MINIMIZED MODE and MAXIMIZED MODE.
40
The range of the PHASE LOSS can be extended to Enabled or Disabled by using the EXPANDED SETTING as described in
section
5.5.5 page 50.
Содержание ASTAT XT QT 0008U Series
Страница 1: ...GE Consumer Industrial ASTAT XT User Manual...
Страница 17: ...17 Technical Specifications 3 4 I O Wiring...
Страница 123: ...Ed 15 03 09 Copyright GE Power Controls 2009...