Control card, 10 V DC output:
Terminal number
50
Output voltage
10.5 V
±
0.5 V
Max. load
25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics:
Resolution of output frequency at 0–1000 Hz
+/- 0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2 ms
Speed control range (open-loop)
1:100 of synchronous speed
Speed accuracy (open-loop)
30–4000 rpm: Maximum error of
±
8 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Vibration test all enclosure types
1.0 g
Relative humidity
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
max. 50
°
C
1)
- with full output power of typical EFF2 motors (up to 90% output current)
max. 50
°
C
1)
- at full continuous Drive output current
max. 45
°
C
1)
1)
For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation
0
°
C
Minimum ambient temperature at reduced performance
- 10
°
C
Temperature during storage/transport
-25 - +65/70
°
C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Control card performance:
Scan interval
5 ms
Control Card, USB Serial Communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
CAUTION
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection ground. Use only isolated laptop/PC as connection to the
USB connector on drive or an isolated USB cable/drive.
Specifications
AF-600 FP Quick Guide
DET-759A
35
8
8