AF-600 3-phase
Recommended fuse size
Recommended max fuse
[kW] / [HP]
11/15
gG-25
gG-63
15/20
gG-32
18.5/25
22/30
gG-40
30/40
gG-63
gG-80
37/50
gG-100
45/60
gG-80
gG-125
55/75
gG-100
gG-160
75/100
gG-125
90/125
110/150
aR-250
aR-250
132/200
aR-315
aR-315
160/250
aR-350
aR-350
200/300
250/350
aR-400
aR-400
315/450
aR-500
aR-500
400/550
aR-550
aR-550
450/600
aR-700
aR-700
500/650
560/750
aR-900
aR-900
630/900
710/1000
aR-1600
aR-1600
800/1150
900/1250
1000/1350
1200/1600
aR-2000
aR-2000
1400/1900
aR-2500
aR-2500
Table 8.6 525-690 V, IP21/Nema 1 and IP55/Nema 12
Specifications
AF-600 FP Quick Guide
42
DET-759A