If 4-20mA output is off-scale low or high and cannot be adjusted using DIAGNOSTICS mode,
IO/Power Supply board may be defective and should be replaced.
CONTROLLER MODBUS DATA INCORRECT
•
Verify that MODBUS master is requesting data from correct data register (31002).
•
Verify that controller MIN and MAX count settings are correct. MIN counts should be “800”
which corresponds to 4mA and MAX counts should be “4000” which corresponds to 20 mA.
•
Verify that the GDS-68XP MODBUS address matches the address programmed into the
controller’s channel configuration.
CONTROLLER SHOWING MODBUS COMM ERROR
•
Check for incorrect MODBUS polarity (swap “A” and “B” if unsure; no damage will occur).
•
Verify that MODBUS master is requesting data from correct MODBUS address.
•
Verify that MODBUS master is requesting data from register 31002.
•
Verify that there are no other MODBUS slave devices with identical MODBUS address.
GDS-68XP DISPLAY BLANK
•
Verify DC power at IO/Power Supply board, TB2, terminals 1 (+24) and 4 (Gnd).
•
Verify ribbon cable connected between IO/Power Supply board and Display Assembly.