DIAGNOSTICS MENU
The Diagnostics page provides tools for use during setup or testing. Tests for optional features are not
available if the feature is not installed.
Figure 9-7: Diagnostics Menu Tree
!! Warning !!
!! Warning !!
!! Warning !!
!! Warning !!
Diagnostic mode.
Alarms will not
Be processed.
Edit
(OK)
Next (Cancel)
Next (Cancel)
Next (Cancel)
Next (Cancel)
Diagnostics
Relays →
Analog Inputs →
Analog Outputs →
LED Test →
Serial Ports →
ADC Readings →
Relays
Relays
Relays
Relays
Relay 1 Off
Relay 2 Off
Relay 3 Off
Fault Relay On
Ch.1 EC - Loc
Counts: 856
Temp: 24.5 degC
—————————————————
Ch.2 4-20mA
Counts: 0
Current: 0.00mA
Analog Outputs
Analog Outputs
Analog Outputs
Analog Outputs
4-20mA Out1 0mA
4-20mA Out2 0mA
Out1 Fdbk 0.07
Out2 Fdbk 0.06
LED Test
Comm Test
Comm Test
Comm Test
Comm Test
Connect Loopback
Port 1 => 2: Bad
Port 2 => 1: Bad
420 Out1: 4.60mA
Fdbk 1: 4.57mA
420 Out2: 4.05mA
Fdbk 2: 4.14mA
Sensor V: 0.01V
SensrAmp: 0.78V
PSU: 22.93V
WARNING – ENTERING DIAGNOSTICS MODE DISABLED ALARM
FUNCTION AND REQUIRES A DEVICE REBOOT ON EXIT.
Relays Menu
Allows individual relays to be turned on or off under user control. Only
available if optional Relay / Modbus board is installed.
Analog Inputs Menu
Shows current input readings for channel 1 and channel 2.
Analog Outputs Menu
Shows the live output values on analog channel 1 and analog channel 2.
Also shows the feedback monitor reading for both channels.
LED Test Menu
Cycles the external LED.
Comm Test Menu
Performs a loopback test to verify proper operation of the serial
components. Only available if optional Relay / Modbus board is
installed
.
ADC Readings
Displays values monitored by internal analog-to-digital converters.