Page 10
3.4 Flue / Chimney.
-
The stove is approved for use with 127mm (5 inch)
diameter insulated Selkirk
insta-lock gas vent.
-
The spigot is designed to be compatible with a
selkirk 5 SIL - DH draft hood connector. The inner
sleeve will require reducing in length so that it
protrudes 25mm below the outer sleeve (See figure
2).
-
Before you install the stove make sure the chimney
flue outlet is correctly positioned to align with the flue
outlet on the stove and that the chimney is in good
condition. If not, a chimney liner must be installed or a suitable class 2 gas flue used.
A draught is necessary to ensure the products of combustion are fully evacuated.
Connect and seal the stove flue collar to the chimney using full depth of collar. The
flue must have a minimum effective height of 3 metres (10ft), however, to ensure
optimum performance we recommend 3.66 metres (12ft) or higher. The flue must be
free of obstruction and any dampers must be fixed in a permanently open position.
Ensure that the chimney is not closed and that it has been swept prior to the stove
being installed. Make sure that rain, birds or any foreign bodies cannot get into the
chimney and cause blockage or damage. This problem can normally be overcome by
fitting an approved gas cowl. It is essential to the effective running of your stove that
the chimney draws properly and allows the products of combustion to escape.
3.5 Ventilation.
-
Normal adventitious ventilation is usually sufficient to satisfy the ventilation
requirements of this appliance. In GB reference should be made to BS5871 Part 1
and in IE reference should be made to the current edition of IS 813 “ Domestic gas
installations” which make clear the conditions that must be met to demonstrate that
sufficient ventilation is available.
-
An extractor fan may only be used in the same room as this appliance, or in any
area from which ventilation for the appliance is taken, if it does not affect the safe
performance of the appliance. Note the spillage test requirements detailed further on
in this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected.
3.6 Location.
This appliance must not be installed in a private garage or any room, which contains
a bath, or shower or where steam is regularly present.
3.7 Propane gas (944 Manual Only).
Propane gas appliances must not be installed in a cellar, basement or other room
which is built entirely below ground level (See Gas Safety (Installation and use)
Regulations)
©
GDC Group Ltd. 2015
INSTALLER GUIDE
Figure 2.