Preparing for commissioning
5
January 2017
America
33 /72
Permissible cooling water data
•
Max. cooling water pressure:
10 bar / 145 psi
•
Min. cooling water inlet temperature:
5 °C / 41 °F
•
Max. cooling water inlet temperature:
42 °C / 107 °F
•
Max. cooling water outlet temperature:
57 °C / 134 °F
P [KW]
Δp [psi]
V [gal/min]
160
13
39.6
200
16
47.5
250
19
52.8
290
34
60.7
Chart 5-1: Cooling water requirement at maximum
power and (
ΔT
= 10K)
ΔT:
Cooling water outlet temperature =
Cooling water inlet tempe ΔT
Δp:
Cooling water outlet pressure =
Cooling water inlet pressure - Δp
The values are based on freshwater quality
without additives (e.g., antifreeze). If the cooling
water quality deviates from this, please consult
Gardner Denver.
Adjust the volume of cooling water according to
the description "Cooling water adjustment for
water-cooled compressor systems".
NOTE
The cooling water outlet temperature should
be below 57 °C / 135 °F, if possible, in order to
prevent excessive lime sediment.