Commissioning and operation
6
January 2017
America
37 /72
3
Unlock the <E-stop> button.
Turn the button counterclockwise.
4
Start up the compressor.
See the paragraph “Commissioning after
a fault” in the chapter “Commissioning and
operation.”
6.3
Routine commissioning
Routine commissioning includes commissioning
after maintenance.
1
Open the shutoff valves between the
compressor and the compressed air network.
2
Then proceed as described in the "Initial
commissioning" section.
6.4
Commissioning after extended
downtime
For commissioning after an extended idle period,
consult Gardner Denver.
6.5
Commissioning after a fault
NOTICE
Property damage
Avoid switching on the compressor multiple
times without clearing the fault, as this can lead
to significant machine damage.
➯
Switch on the compressor only after the
fault has been cleared.
Recommissioning after a fault (automatic
shutoff)
Faults are shown in the "Fault memory" display
memory.
1
Switch off the main disconnect switch and
secure it against switching on again.
2
Clear the fault.
See the “fault correction” chapter.
3
Switch on the main disconnect switch.
4
Acknowledge the fault in the Fault memory
menu.
5
After acknowledgement, the message [Ready
to start] appears on the display, as long as no
other fault is present.
6
Press the start button < I > on the control
panel.
– The compressor switches on.
– The compressor runs in automatic mode.
See the sequence description in the
"Sequence (automatic operation)" section of
the chapter "Structure and function."
Содержание L160 110A V2
Страница 1: ...User manual Screw compressor L160 L290 V2 L160RS L290RS V2 America ZS1149274 03 January 2017...
Страница 7: ...Foreword 1 January 2017 America 7 72 1 6 Rating plate Fig 1 1 Rating plate...
Страница 69: ...Appendix 9 January 2017 America 69 72...
Страница 70: ...9 Appendix 70 72 America January 2017...
Страница 71: ...Appendix 9 January 2017 America 71 72...