background image

- 8 -

5

f

d

m

k

V

1

 / PM7

3.08

7. Fault finding
7.1 Pump overload

1. Measurement of delivery  pipe back-pressure and ex-

change of candle filters if necessary.

2. Checking of mechanical rotation of compressor stages

at motor fan. The pump should be dismantled and
cleaned if excessive resistance occurs (possibly prod-
uct-induced).

7.2. Loss of vacuum

Check vacuum at suction flange, clean screen if neces-
sary.

Check excess pressure in delivery pipe (back pressure
should not exceed 0.3 bar).

If the ultimate vacuum is not attained, proceed as fol-
lows:
Remove and clean screen in suction flange.
Check vacuum between LP-, MP- and HP-stages (re-
move screw plug and measure vacuum).  If the same
vacuum is measured at the suction flange and the MP-
vacuum measuring point, the LP-stage is defective. If
the pressure measured at the MP-vacuum measuring
point, the MP-stage is close to the value at the HP-
vacuum measuring point, the MP-stage is defective. If
the pressure measured at the HP-vacuum measuring
point is close to atmospheric pressure, the HP-stage is
defective (see Fig. 2, page 4).

7.3. High oil consumption

Excessive oil consumption by the fresh oil lubrication system
will necessitate replacement of the check valves in the oil pipes.

8 Instructions for storing fresh oil lubricated rotary vane

vacuum pumps

Introduction

Start-up of all pumps delivered by Rietschle should be
made within 3 months. If this is not possible, please
observe the following details, the guarantee given by
Rietschle may be invalidated if not followed.

a. Storing of pumps

The store room for the pumps must be dry and free of all
corrosive materials. The ambient temperature should be
constant and above 10°C.

b. Condition of Stored Pumps

The suction and discharge ports of the pumps should be
sealed with blank flanges. All lubricating and sealing oil
reservoirs should be filled, in accordance with the
instruction manual.

c. Maintenance during Storage

The pumps should be operated once a month for about
2 hours to prevent any kind of corrosion within the pump.
Please pay attention to the fact, that the blank flange
from the discharge side is to be removed before operation
and installed again afterwards. The blank flange of the
suction side should not be removed, since end vacuum
should be reached.

d. Setting Pumps into Operation

A technical service made by Rietschle will be necessary
for all pumps stored longer than 3 months. You will be
responsible for the costs of the inspection and test run.
Further, all costs occurring from improper storage or
handling will be charged.

6.2 Oil mist separator

(Exhaust side accessory)
Oil mist separators are flanged directly onto the vacuum pump
exhaust flange. Separation invariably takes place in two stages:

separation of liquid droplets in the condensate receiver.

separation of aerosols in the candle filters.

Oil mist separators are available in three different materials for
the chemical-pharmaceutical industry.

stainless steel 1.4541

stainless steel 1.4541, halar-coated

The candle filters are made of Teflon to guarantee complete
resistance to solvents and partial resistance to acids.
Note.  It is not advisable to employ this method of separation
with products which polymerise or become resinous.  The filters
clog rapidly and necessitate intensive maintenance and costly
exchange of filters.

6.2.1 Maintenance of oil mist separators

 (fig. 5)

Increased power consumption by the drive motor owing to
higher filter resistance of the oil mist separator necessitates
exchange of candle filters and cleaning of reservoirs.
Exchange of candle filters: oil reservoir cap (d) and O-ring may
be removed by opening. Release retaining cap (m), exchange
candle filters (f) and check for correct fitting.  The condensate
and oil mixture formed should also be discharged regularly,
manually or automatically, during operation of the pump. A level
monitor (V

1

) is normally fitted, to switch off the pump automati-

cally at the appropriate level.

Содержание Elmo Rietschle VLV Series

Страница 1: ...80 2 VLV 80 3 VLV 100 2 VLV 100 3 Gardner Denver Schopfheim GmbH Postfach 1260 79642 SCHOPFHEIM GERMANY Fon 49 7622 392 0 Fax 49 7622 392 300 e mail er de gardnerdenver com www gd elmorietschle com B...

Страница 2: ...uumpumpen VLV 5 3 2 14 Einsatzgrenzen VLV 5 4 Installation und Inbetriebnahme 5 4 1 Mechanische Installation 5 4 1 1 Aufstellung 5 4 1 2 Saugseite 5 4 1 3 Abluftseite 5 4 2 Elektrische Installation 6...

Страница 3: ...len oder ein Ausfall derVakuumpumpezueinerGef hrdung vonPersonenoderEinrichtungenf hrt sind entsprechende Sicherheitsma nahmen anlagenseits vorzusehen 3 Ausf hrungen und Aufbau 3 1 Ausf hrungen Die Ty...

Страница 4: ...er 3 bzw 2 Stufen und das obere Rotorlager mit Frisch l versorgt Die lschmierpumpe hat 4 Schmierstellen bei der VLV 2 bzw 6 Schmierstellen bei der VLV 3 Bei der Lagerschmierung flie t das l vom oberen...

Страница 5: ...Dauer f r den Vor und Nachlauf liegt bei ca 20 30 Minuten Ausreichende K hlm glichkeit der Pumpe mu vorhanden sein siehe 4 1 1 Aufstellung berpr fen ob die Umgebungsluft stark aggressiv ist da evtl A...

Страница 6: ...f r Motor und f r die Steuerung der Kontroll Einrichtungen befinden sich im Klemmenkasten Jede Anschlu klemme der Klemmenleiter hat eine Nummer und alle Anschl sse f r Motor und Kontroll Organe sind...

Страница 7: ...ge Weniger l Mehr l lschmierpumpe VLV 25 2 25 3 40 2 40 3 60 2 60 3 80 2 80 3 100 2 100 3 50 Hz 0 065 0 097 0 065 0 097 0 065 0 195 0 065 0 195 0 065 0 195 60 Hz 0 078 0 117 0 078 0 117 0 078 0 234 0...

Страница 8: ...t bersteigen Wird das Endvakuum nicht erreicht folgende Arbeiten durchf hren Sieb im Saugflansch ausbauen und reinigen berstr mventile ausbauen auf Funktion berpr fen Vakuum zwischen ND MD und HD Stuf...

Страница 9: ...0 2 VLV 80 3 VLV 100 2 VLV 100 3 Gardner Denver Schopfheim GmbH Postfach 1260 79642 SCHOPFHEIM GERMANY Fon 49 7622 392 0 Fax 49 7622 392 300 e mail er de gardnerdenver com www gd elmorietschle com Vac...

Страница 10: ...y 5 4 Installation and commissioning 5 4 1 Mechanical installation 5 4 1 1 Installation 5 4 1 2 Suction side 5 4 1 3 Exhaust 5 4 2 Electrical installation 6 4 2 1 General 6 4 2 2 Electrical connection...

Страница 11: ...planned shut down of the pump could possibly cause harm to persons or installations then the corresponding safety backup system must be installed 3 Design and Construction 3 1 Models The VLV range is...

Страница 12: ...ntainer the oil passes through an overflow orifice back into the fresh oil reservoir 3 2 5 Oil separation The oil containing exhaust flows from the HP stage into the used oil and condensate reservoir...

Страница 13: ...cations Vacuum for printed circuit board production Carbonisation in drink production Vacuum packaging of moist products Vacuum cooling of foods Vacuum filtration Vacuum drying Vacuum crystallisation...

Страница 14: ...numbered and all connections for motor and monitoring elements are allocated a specific number see circuit diagram Connection numbers must be observed during refitting or repair work to simplify detec...

Страница 15: ...tion for VLV l hr Oil Consumption for VLV Roots booster on request VLV 25 2 25 3 40 2 40 3 60 2 60 3 80 2 80 3 100 2 100 3 50 Hz 0 065 0 097 0 065 0 097 0 065 0 195 0 065 0 195 0 065 0 195 60 Hz 0 078...

Страница 16: ...the instruction manual c Maintenance during Storage The pumps should be operated once a month for about 2 hours to prevent any kind of corrosion within the pump Please pay attention to the fact that t...

Отзывы: