background image

PP610/612 LED lighting controllers - User Manual

2

Safety

Read this before using the PP610. Always observe the following safety
precautions. If in doubt, contact your distributor or Gardasoft Vision. The
following symbols mean:

Warning:

Read instructions to understand possible hazard

Warning:

Surface may get hot.

Warning:

Possible hazardous voltage.

Where these symbols appear in the manual, refer to the text for
precautions to be taken.

2.1

Heat

Ensure the PP610 is mounted correctly (see

Section 6, Mechanical fixing

),

and that you do not exceed any of the ratings for the unit (see

Section 11,

Reference information

).

At its maximum ratings, the PP610's enclosure can exceed 75°C which is
sufficient to cause a burn if touched. Place in a position where personnel
cannot accidentally touch it and ensure there is a free flow of air around
the unit.

2.2

Electrical

The PP610 produces high energy pulses. Take care to connect the
outputs correctly and protect the output wiring and load from any short
circuits. When switched off, energy remains stored in the PP610 for about
15 seconds.

The PP610 does not have complete tracking isolation of inputs and
outputs, therefore, please observe the following guidance:

Computer equipment that is connected to the communication or trigger
ports must be internally powered or separated from mains electricity by
double insulation/reinforced isolation or be approved to IEC 60950-1
standard. All other equipment connected to the triggers or other ports
must also have double insulation/reinforced isolation protection from the
mains supply.

The Power Supply Unit (PSU) used to energise the PP610 must provide
double insulation/reinforced isolation from mains electricity and protected
against short circuits and overloads. We recommend using a PSU that lim-
its its output current to the appropriate rating of the controller by design,
by setting the current limit on the supply (if possible), or through over cur-
rent protection. The PSU should be approved to either IEC 60950-1, IEC

6

Содержание PP610

Страница 1: ...PP610 612 LED Lighting Controllers Issue 015 User manual www gardasoft com...

Страница 2: ...his equipment cannot cause any dangerous situation or significant financial loss to occur Deliberate acts of endangerment and vandalism are not covered by this document and must be considered by the i...

Страница 3: ...onnections 19 8 1 PP610 serial connector 20 8 2 PP612 CCS connectors 21 8 3 Power supply 22 8 3 1 Single supply applications 22 8 3 2 Split supply applications 24 9 Operation 25 9 1 Startup 25 9 2 Col...

Страница 4: ...PP610 612 LED lighting controllers User Manual 10 4 Pulsed mode output 43 11 Reference information 45 12 Timings 46 12 1 Selected continuous mode 46 12 2 Pulse mode 46 13 Error codes 47...

Страница 5: ...ote that the supply voltage must be connected to three terminals When the PP610 powers up it should show two alternating lines on the display to indicate that it is operating properly Read Section 9 O...

Страница 6: ...o connect the outputs correctly and protect the output wiring and load from any short circuits When switched off energy remains stored in the PP610 for about 15 seconds The PP610 does not have complet...

Страница 7: ...roller must be externally fused to 4A using a slow blow fuse T4AH 50V The installer must provide a clearly marked nearby and easily accessible switch as part of the installation to allow the controlle...

Страница 8: ...hentliche Ber hrung durch das Personal ausgeschlossen ist und stellen Sie sicher dass Luft frei um das Ger t zirkulieren kann 3 2 Elektrik Das PP610 erzeugt Impulse mit hoher Energie Achten Sie darauf...

Страница 9: ...sofern angebracht gesch tzt sein Die Verkabelung der Stromversorgung zur Steuerung muss f r min destens 4 A bemessen sein Die Verkabelung vom Kanalausgang zur Last muss h her als der maxi male Kanala...

Страница 10: ...ts beeintr chtigt werden 3 4 Installationsanleitung Haftungsausschluss Diese Informationen dienen nur zur Orientierung Installationstechniker m ssen ihre eigene spezifische Risikobewertung f r die jew...

Страница 11: ...e pas de le toucher par accident et veillez ce que l air circule librement autour de l unit 4 2 lectricit Le PP610 produit des impulsions d nergie lev es Veillez bien raccorder les sorties et ce que l...

Страница 12: ...tie de la cha ne la charge doit avoir une capacit sup rieure au courant de sortie maximal de la cha ne Si le contr leur est mal r gl ou en cas de panne l nergie fournie par l alimentation au contr leu...

Страница 13: ...ment titre indicatif Les installateurs doivent effectuer leur propre valuation des risques pour chaque installation M me si Gardasoft Vision Ltd a pr par minutieusement ces conseils Gardasoft Vision L...

Страница 14: ...large variations in light output Currents can be specified in 0 25mA steps below 1A and in 1mA steps above 1A Three modes of operation are provided separately for each channel Continuous In continuou...

Страница 15: ...into the enclosure by more than 6mm The enclosure of the PP610 is used to dissipate power in the form of heat For this reason the material to which the unit is attached must be suitable preferably met...

Страница 16: ...PP610 together Chose a PSU that limits its output current by design by setting the current limit on the supply if this feature exists or use fuses Remember to de rate the fuse if mounted in an enclos...

Страница 17: ...L Voltage across the light LD1 and LD1 for output 1 This is usually easy to calculate as the voltage across the light is normally the voltage rating of the light as declared in its specification Alter...

Страница 18: ...than 10W no heatsinking is required If the heat output is between 10W and 24W the PP610 needs to be mounted on a solid piece of metal to dissipate the heat Above 24W it is necessary to have a large h...

Страница 19: ...The power connector has the following connections Screw terminal ID Function GND1 Channel 1 Power supply VS1 Power supply LD1 Load LD1 Load VS Digital power supply GND Digital power supply GND LD2 Ch...

Страница 20: ...tor PP610 and PP612 controllers are fitted with a standard 9 way D sub female connector for RS232 communications The connections are shown in the diagram below A standard straight through cable can be...

Страница 21: ...not labelled on the case Refer to the table below and the diagram overleaf for the layout Connector Channel Use SKT9 1 CCS 12V lights SKT10 1 CCS 24V and HLV lights SKT12 2 CCS 12V lights SKT11 2 CCS...

Страница 22: ...Section 8 3 1 Single supply applications It is possible to run the two channels and digital system from two or three separate supplies as shown in Section 8 3 2 Split supply applications though this w...

Страница 23: ...PP610 612 LED lighting controllers User Manual Note A PP600 is shown in these illustrations The same power connections apply for a PP610 or PP612 23...

Страница 24: ...supply applications It is possible to run the two channels and digital system from two or three separate supplies as shown below though this will rarely be necessary Note It is essential that the grou...

Страница 25: ...l of the PP610 can operate in three ways Continuous output CON The output current is fixed Selected continuous output SE 1 SE 2 SE12 One or both inputs can be used to select an output current For each...

Страница 26: ...off by default When a trigger is received on one of the digital inputs the PP610 will wait for a delay period and then pulse the output The delay period pulse width and pulse current are all configura...

Страница 27: ...ry default the maximum rating is set to 4A 9 3 5 Setting numeric values When the PP610 displays numeric values for the user to change the right hand digit flashes to indicate that the p and q buttons...

Страница 28: ...and q buttons to select the required current in Amps Note Refer to Section 9 3 5 Setting numeric values Press SELECT dONE is displayed for one second The PP610 sets the output current 9 4 2 Setting p...

Страница 29: ...T2 DEL is displayed Wait for one second Use the p and q buttons to select the required delay in milliseconds Note The delay is set in multiples of 20ms Note Refer to Section 9 3 5 Setting numeric val...

Страница 30: ...he required current in Amps Note Refer to Section 9 3 5 Setting numeric values Press SELECT dONE is displayed for one second The PP610 is ready to pulse the output on a trigger When the lights are pul...

Страница 31: ...o be set up It is entered by holding the RANGE button down for one second In order for the whole range of timing values to be entered it is necessary to specify whether the delay is in seconds or mill...

Страница 32: ...ct which output channel to set up CH1 or CH2 Press SELECT rAT is displayed Wait one second Use the p q and RANGE buttons to select the maximum current rating of the LED unit Press SELECT Use the p and...

Страница 33: ...the current in Amps a or C 3 to enter the current in milliamps b Press SELECT a b Use the p and q buttons to select the required current in Amps a or milliamps b Note Refer to Section 9 3 5 Setting n...

Страница 34: ...d q buttons to select which output channel to set up CH1 or CH2 Press SELECT rAT is displayed Wait one second Use the p q and RANGE buttons to select the maximum current rating of the LED unit Press S...

Страница 35: ...ct d0 to enter the delay in seconds a or d 3 to enter the delay in milliseconds b Press SELECT a b Use the p and q buttons to select the required delay in seconds a or milliseconds b Note Refer to Sec...

Страница 36: ...enter the pulse width in seconds a or P 3 to enter the pulse width in milliseconds b Press SELECT a b Use the p and q buttons to select the required pulse width in seconds a or milliseconds b Note Ref...

Страница 37: ...t in amps a or C 3 to enter the current in milliseconds b Press SELECT a b Use the p and q buttons to select the required current in amps a or milliamps b Note Refer to Section 9 3 5 Setting numeric v...

Страница 38: ...ut channel to be specified For these the channel number either 1 or 2 immediately follows the two letter command Where more parameters are needed they consist of a single upper case letter defining th...

Страница 39: ...he settings to memory AW Once the settings are saved to memory they are then retained when the unit is switched off If this is not done changes to the settings are volatile and if the unit is switched...

Страница 40: ...s 1 and 2 and Output channel 2 set up to pulse a current of 5 35A for 100ms using input 1 as a trigger and a delay of 15ms with a de bounce period of 20ms The result of the ST command will be 01 M 06...

Страница 41: ...us current Set the output current RCfCcVvEe Where f output channel 1 or 2 c output selection Set to 0 for non selected operation v output current in milliamps e maximum current rating of the LED This...

Страница 42: ...nd must be sent for all output selections specified by the mode command If a single input is selected two current settings are needed for selections 0 and 1 If both inputs are selected four current se...

Страница 43: ...and will not allow a delay to be set which is less than the minimum for the current setting When changing current and delay values it may be necessary to use the RT command to set the delay to a highe...

Страница 44: ...ting of the LED This is optional if not required omit Ee from the command In the following example output channel 1 is set to pulse a current of 5 35A for 9ms triggered by input 1 with a delay of 8ms...

Страница 45: ...ble level IPH Input disable level IPL 24 IPH 4 5V IPL 1V This is the voltage applied between the anode and cathode of each optically isolated input Output current per channel 4A continuous or10A pulse...

Страница 46: ...ven for channel 1 and assume a trigger input signal of 5V The delays are approximately 8 s shorter for a 24V trigger input The delays for channel 2 are greater All timings are given in microseconds Pr...

Страница 47: ...E16 When the unit has powered up the non volatile memory was corrupt and has been cleared Set up the unit again E25 E26 The PP610 is calibrated during manufacture This stored calibration has become i...

Страница 48: ...PP610 612 LED lighting controllers User Manual Code Meaning E17 E40 E41 E64 E65 E67 E74 An internal software error has occurred Make a note of the number and contact your distributor 48...

Страница 49: ...PP610 612 LED lighting controllers User Manual This page is left blank for your notes 49...

Страница 50: ...ay 2017 Copyright 2017 Gardasoft Vision Ltd Gardasoft Vision Ltd Trinity Court Buckingway Business Park Cambridge CB24 4UQ UK tel 44 1954 234970 fax 44 1954 231567 Gardasoft LLC Oak Ridge Road Weare N...

Отзывы: