G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
MegaV2 250 Installation Guide, Release 2.2
56
8.
M
EGA
V2 250
SPECIFICATIONS
Table 7: Technical specifications
MEGA.V2 250
T
ECHNICAL
D
ATA
Topology
True on-line, double-conversion, VFI
Construction
Modular, parallel hot-swapped modules
Operation
Continuous
Input
Voltage
3×
400
Vac + N
Voltage range
–20 % and +15 %
Current
3x42 A per module – no inrush current at startup
Frequency
47–63 Hz
Power walk-in
>60 s
Power factor
0.99
THDI
<5 %
Output
Rated power
25 kVA / 25 kW to 250 kVA / 250 kW
Frequency (in free-running mode)
50/60 Hz ±0.1 %
Frequency tracking range
±0.5 Hz, ±1 Hz, ±2 Hz, ±3 Hz (selectable)
Slew rate
1 Hz/sec
Voltage
3 ×N
Static regulation
±1 %
Regulation for unbalanced load
±1 % for 100 % unbalanced load
Dynamic response to 100 % load step
±2 %
Overload
110 % : 10 min; 125 % : 60 s; 1000 % : 1 cycle
Waveform
Sinusoidal
THD
Less than 2 % for linear load
Load CF (max)
6:1
Ac-Ac efficiency (nominal)
Up to 96 % at full load
Dc-Ac efficiency (nominal)
Up to 98 % at full load
Batteries
Dc-Link voltage
±320 Vdc to ±405 Vdc
Quantity
60×12 V
Type
Sealed, lead acid, rechargeable
Display
TFT LCD 7" color monitor with touch screen
General
Maximum power dissipation (Po=25 kW)
N*1041 W (N*3552 BTU/h)
Ambient temperature
-10
°
C to +40
°
C (operating), -20
°
C to +60
°
C (storage)
Relative humidity
95 % max (non-condensing)
Altitude
1500 m without derating
Enclosure
IP20
Cooling system
Forced air (multi-fan with speed control)
Standards
EMC
IEC 62040-2
Design
IEC 62040-3
Safety
IEC 62040-1
Low magnetic field radiation
EMF as per ICNIRP
System weight and dimensions
UPS capacity (kVA)
25
50
75
100
125
150
175
200
225
250
UPS weight (kg)
190
223
256
289
322
355
388
421
454
487
System dimensions (mm)
1970 (H) x 670 (W) x 655 (D)
Module weight and dimensions
Weight
33 kg
Capacity
25 kVA / 25 kW
Height
135 mm
Width (not including connectors)
455 mm
Width (including connectors)
535 mm
Depth
655 mm
All specifications are subject to change without notice.