MegaV2 250 Installation Guide, Release 2.2
54
B a t t e r y C h e c k s
Turn the battery circuit breaker to Off and disconnect all Anderson connectors in the battery set.
Record the battery serial number, type, and number of cells in the table below:
Battery manufacturer
Battery model
Rating (Ah)
Number of strings (x 32)
Use a power resistor of 0.5
Ω
(300 W rating recommended) for the load to check the voltage drop
across the terminals of each battery. The voltage measured across the resistor should be no less
than 10 Vdc for any battery. Replace any batteries that seem to be inadequate.
BATTERY STRING #1
BATTERY STRING #2
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
1
16
31
46
2
17
32
47
3
18
33
48
4
19
34
49
5
20
35
50
6
21
36
51
7
22
37
52
8
23
38
53
9
24
39
54
10
25
40
55
11
26
41
56
12
27
42
57
13
28
43
58
14
29
44
59
15
30
45
60
END OF MAINTENANCE PROCEDURES REPORT