AC Input Voltage
120/240V single phase, or 120/208V three phase.
Input Current: 120 amps maximum
Output: Six, 120V 20A circuits
Maximum AC Current Rating
Six, 120V 20A circuits for 120A total.
Cable Clamp
145R - 1 1/2 inch NM Clamp Type - Wire Size: 2 to 6AWG
AC Output Receptacles
Rear Panel Outlets: 6 duplex NEMA 5-20R sequenced.
Front Panel: 6 thermal circuit breakers, one per duplex pair.
Operating Temperature and Humidity
5 to 40C (40 to 105F), <90% Relative Humidity
User Interface
Key-switch: Front panel, 3 position (On/Off/Remote)
Keys: Included, 1 pair
Push Button Switch: Front panel
Circuit Breakers: Front panel, push-button; 6, 20A Thermal Breakers
Output Circuit Status: Front panel indicators – one per output
Configuration Switches: Front panel, hidden by security cover;
3 maximum delay switches – 1, 2, and 4 minute
Force Off NO/NC, 12V mode On/Off, GND mode On/Off,
Momentary/Maintained mode selection
Fine Delay Adjustment: Potentiometer hidden by security cover.
SPECIFICATIONS
Control/Status/Triggering (Rear Panel)
Remote Terminal: Phoenix 4 Pin Connector with Screw Terminals;
+12V @ 250mA, STAT, REM, GND (Class 2 wiring)
+5 to 30VDC at REM terminal.
Delay Outputs: Phoenix 8-Pin Connector with Screw Terminals
6 relay contacts with NO and NC common connections
(Class 2 wiring)
A, B, C, D, E, and F delay contacts switched with output circuits
Force Off: Phoenix 2 Pin Connector with Screw Terminals;
Optically isolated, 12V, 10mA current source (Class 2 wiring)
Senses external relay contact closure
Power Consumption
Standby: 5 Watts
Sequenced ON: 20 Watts
Safety Agency
Intertek, FCC, RoHS Compliant