CN-2400S Controls two ASD-120 2.0 Sequencers with an optional Fire Alarm Force OFF.

Diagram #5 illustrates a Furman CN-2400S Contractor Series controlling two 
ASD-120 2.0 sequencers with a fire alarm providing an emergency FORCE OFF:

1. CN-2400 S DELAY 3 RELAY OUTPUT (NC) and (C) terminals connect appropriately to 
    both ASD-120 2.0 units per the 12V and REM terminals with a parallel connection.

   • (NC) to both 12V and (C) to both REM. 

2. Configure Multi-Function DIP on the CN-2400S, factory default with DIP 4 UP.

   • DIP 4 UP – (NO), verify factory default.
◦  • CN-2400S DIP 2 is also set UP for a longer delay time.

3.  Fire alarm contacts connected to FORCE OFF terminals on both ASD-120s 
    (parallel connection).

   • Configure DIP 4 switch on ASD-120 2.0 to NO or NC depending on the contact type.  
      used at the fire alarm.  Typically NC is the best terminal option for Event Production.
   • Configure Multi-Function DIP on each ASD-120 2.0, factory default with DIP 4 UP.
   • All Delay Bank LED indicators will flash when FORCE OFF is activated.
   • Optionally, the fire alarm contacts can also be connected to the FORCE OFF terminals of the  
      CN-2400 S if desired.

4. Configure ASD-120 2.0 Multi-Function DIP for Normally Closed & Maintained Mode ON

   • DIP 4 UP – (NO), verify factory default.
   • DIP 7 DOWN – MNT, verify factory default.
   • ASD-120 2.0 DIP 1 is also set UP for a shorter delay time. 

TWO ASD-120 2.0 UNITS CONTROLLED BY A CN-2400S AND BY FIRE ALARM

1      2     3     4     5      6     7            

ON

1      2     3     4     5      6     7     8     9             

ON

1      2     3     4     5      6     7     8     9             

1      2     3     4     5      6     7            

ON

FORCE OFF

DELAY 3

NO

NC

C

FO

FO

CN-2400S DIP SETTINGS

CN-2400S DIP SETTINGS

ASD-120 2.0 DIP SETTINGS

ASD-120 2.0 DIP SETTINGS

FIRE ALARM 

SYSTEM TRIGGER

+12V

STAT

REM

GND

REMOTE PORT

OPTIONAL 
REMOTE 
SWITCH

REMOTE

12V  STAT  REM  GND

FORCE OFF

FORCE OFF

NO

C

NC

REMOTE

12V  STAT  REM  GND

When the CN-2400S is sequenced ON, the CN-2400S unit’s DELAY 3 Contact Relay will trigger both 
ASD-120 2.0 units to begin their respective programmed sequence.

Caution:

 The OFF sequence for the CN2400S and ASD-120 2.0 units will start at the same time.  

In order to avoid timing conflicts while ramping down, the CN-2400S should be set to a longer delay time interval than all the time intervals on each ASD-120 2.0 sequencer.

ASD-120 2.0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS-1 SWITCH

ON

ON

CN-2400S

 DIP SETTINGS

ASD-120 2.0 DIP SETTINGS

FIRE ALARM 

NO  C   NC

FORCE 

REMOTE

12V  STAT  REM  GND

12V  STAT  REM  GND

DLY

ADJ

1    2    3    4     5    6    7 

ALWAYS ON 

 ALWAYS OFF 

S

E

Q

*SET TO MIDDLE POSITION

DELAY OUTPUTS

NC   A    B    C    D    E    F   NO

12V  

12V  

REM 

1      2     3     4     5      6     7     8     9

ON

CN-2400S

 DIP SETTINGS

1      2     3     4     5      6     7     8     9

ON

CN-20MP

 DIP SETTINGS

1      2     3     4     5      6     7     8     9

ON

CN-20MP

 DIP SETTINGS

1      2     3     4     5      6     7     8     9

ON

CN-20MP

 DIP SETTINGS

1      2     3     4     5      6     7     8     9

ON

CN-20MP 

DIP SETTINGS

1      2     3     4     5      6     7     8     9

12V  

12V  

12V  

12V  

REM 

REM 

REM 

REM 

REM 

Diagram Example #6

An ASD-120 2.0 Sequencer is controlled by a single RS-1 Remote System Control Panel and the
ASD-120 2.0 remotely activates Furman Contractor Series Products with Bank DELAY OUTPUTS A through F.

Diagram #6 illustrates a Furman ASD-120 2.0 sequencer controlling six Furman Contractor Series 
units and a fire alarm provides an optional FORCE OFF:

1. Connect CN-2400S and CN-20MP REM terminal pins to ASD-120 2.0 DELAY OUTPUT (NC)..
 
2. Connect a 12V terminal pin from each CN-2400S and CN-20MP to an appropriate 
    A through F pin at the ASD-120 2.0 DELAY OUTPUT interface.

3. Configuration Multi-Function DIP on the CN-2400S units are factory default with DIP 4 UP.

    • Only DIP 1 is set DOWN for a shorter than ASD-120 2.0 delay time on each CN-2400S unit. 

4. Configuration Multi-Function DIP on the CN-20MP units are factory default with DIP 4 UP.

    • Only DIP 1 is set DOWN for a shorter than ASD-120 2.0 delay time on each CN-20MP unit. 

5. Optionally, a fire alarm can be connected to FORCE OFF 
    at the ASD-120 2.0, if desired.

   • Configure Multi-Function DIP on the ASD-120 2.0, factory 
      default with DIP 4 UP.
   • All Delay Bank LED indicators will flash when FORCE OFF 
      is activated.

6. RS-1 terminals are connected to the ASD-120 2.0 
   REMOTE terminals, pole to pole:

  

   • 12V to 12V, REM to REM, STAT to STAT, and GND to GND.

7. Configure ASD-120 2.0 Multi-Function DIP for 
    Normally Closed and Maintained Mode ON. 

   • ASD-120 2.0 DIP 2 is set UP for a longer delay time than 
     Contractor Series units. 
   • DIP 4 UP – (NO), verify factory default.
   • DIP 7 DOWN – MNT, verify factory default.
   • Ensure all Bypass Set DIP switches are SEQ.
   • Set ASD-120 2.0 Key Switch to Remote.

ON/OFF Sequences are triggered by the RS-1 Key Switch or by the rotating the Key Switch to ON at the ASD-120 2.0 as an RS-1 override. 

 

DIAGRAM EXAMPLE 5

 

DIAGRAM EXAMPLE 6

Содержание ASD-120 2.0

Страница 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Страница 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Страница 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Страница 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Страница 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Страница 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Страница 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Страница 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Страница 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Страница 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Страница 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Страница 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Страница 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Страница 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Страница 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Страница 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Страница 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Страница 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Страница 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Страница 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Страница 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Страница 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Страница 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Страница 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Отзывы: